Wachendorff DA9602 Operating Manual Download Page 15

 Operating manual 

 

 

 

- 15 - 

10.2  Calibration and factor setting 

All inputs are factory calibrated and recalibration should only be done by qualified personnel. If you 
are not familiar with these procedures do not attempt to calibrate this instrument. 
The calibration steps are: 

a)

 Configure the input type to be calibrated. 

b)

 Configure the lower and upper indication limits for the maximum span of the selected input type. 

c)

 Connect to the input terminals a signal corresponding to a known indication value a little above the 

lower display limit. 

d)

 Access  the  parameter



. With the keys 

 

 and 

 

 adjust the display reading to match the applied 

signal. Then press the 

 

 key to store. 

e)

 Inject a signal that corresponds to a value a little lower than the upper limit of indication. 

f)

 Access the parameter



. With the keys 

 

 and 

 

 adjust the display reading to match the applied 

signal. Then press the 

 

 key to store. 

Note:

 

When checking the controller calibration with a Pt100 simulator, pay attention to the simulator minimum 

excitation current requirement, which may not be compatible with the 0.170 mA excitation current provided by 
the controller.

 

11. Copyright 

The contents of this document are the property of the company Wachendorff Prozesstechnik GmbH 
& Co. KG. Copying or reproduction is prohibited without prior approval. Contents of this document 
refer to the device described therein. 

12. Disclaimer 

All technical content within this document can be modified without notice. The content of this 
document is content of a recurring audit. 
In losses due to fire, earthquake, interventions by third or other accidents or intentional or 
accidental misuse or incorrect using or using under unnormal conditions, repairs will be invoiced. 
Wachendorff Prozesstechnik is not liable for inadvertently loss due using or not using this product, 
such as loss of business income. Wachendorff Prozesstechnik is not liable for cases of an 
unnormal usage. 

13. Other regulations and standards 

WEEE Informationen 

Disposal of old electrical and electronic equipment (as in the European Union and other 
European countries with separate collection systems).This symbol on the product or on its 
packaging indicates that this product may not be treated as household waste. Instead, it 

should be taken to an applicable collection point for the recycling of electrical and electronic 
equipment. If the product is disposed of correctly, you will help prevent potential negative 
environmental factors and human health, which could otherwise be caused by inappropriate 
disposal. The recycling of materials will help to conserve natural resources. For more information 
about recycling this product, please contact your local city office, your household waste disposal 
service or the shop where you purchased the product. 

14. Techncal  Support 

If you have any problems or questions please contact us at:  

 

 
Industriestraße 7 • 65366 Geisenheim 
Tel.: +49 6722 9965-544

 

Fax: +49 6722 9965-78 
E-Mail: [email protected] 
Homepage: www.wachendorff.de/wp 

Summary of Contents for DA9602

Page 1: ...ndorff Prozesstechnik GmbH Co KG Industriestra e 7 D 65366 Geisenheim Tel 49 6722 9965 20 Fax 78 All Information without warranty errors and changes reserved Universal display DA9602 Operating manual...

Page 2: ...on 6 4 10 F1 and F2 function keys 6 4 11 Overflow alarm 7 4 12 Minimum and maximum 7 4 13 24 VDC auxiliary voltage source 7 4 14 Interface 7 5 Installation 7 5 1 Mechanically installation 7 5 2 Electr...

Page 3: ...vent dangerous situations on machinery and installations Machinery and intallations must be designed that fault conditions can not lead to harmful situations to operating personnel e g by independent...

Page 4: ...mocouple K Range 150 C to 1370 C 238 F to 2498 F Thermocouple T Range 160 C to 400 C 256 F to 752 F Thermocouple N Range 270 C to 1300 C 454 F to 2372 F Thermocouple R Range 50 C to 1760 C 58 F to 320...

Page 5: ...oint defined by ALrF SPA1 using alarm 1 as an example ALrF PV ALrF SPA1 ALrF PV ALrF SPA1 SPA1 positive SPA1 negative Alarm of the Maximum Differential Value It triggers when the value of the PV is ab...

Page 6: ...ory and can also be presented at the indicator display by choosing TOTAL screen which is identified by the symbol TOT This symbol is always presented when the TOTAL is being presented The TOTAL value...

Page 7: ...W identify if the part being displayed is the SP most significant part HIGH or the least significant part LOW The totalization alarm SP is defined through the values SPA1 and SPA2 This two parameters...

Page 8: ...e 5 3 Recommendations for the installation To minimize the pick up of electrical noise the low voltage DC connections and the sensor input wiring should be routed away from high current power conducto...

Page 9: ...cording to the desired behavior The user shall understand the importance of each parameter and determine a valid condition or a valid value for each one of them The configuration parameters are groupe...

Page 10: ...SP decimal point SetPoint Alarm Alarm SP Value that defines the point of activation of the alarm outputs For the alarms programmed with the functions of the type Band and Differential these parameter...

Page 11: ...indication range when the input types of 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V are used Defines the function to be executed by F1 and F2 keys No associated function Executes Batch Function Addition...

Page 12: ...p the Level of Protection See Table 03 Frequency Frequency of the local electrical network Serial number 4 most significant digits Serial number 4 least significant digits 8 6 Password protection The...

Page 13: ...in the event of it being forgotten The Master Password doesn t grant access to all parameters only to the Password Change parameter After defining the new password the protected parameters may be acce...

Page 14: ...0 mV 10 M 0 to 5 V 0 to10 V 500 k 4 to 20 mA 100 Measuring of the Pt100 3 wire type 0 00385 with compensation of the cable length max 50 meters excitation current of 0 170 mA OUTPUT Output ALARM1 Rela...

Page 15: ...nical content within this document can be modified without notice The content of this document is content of a recurring audit In losses due to fire earthquake interventions by third or other accident...

Reviews: