Safety cut out
This heater is fitted with a safety over heat cut out.
If the heater will not work the over heat cut out may have operated. To reset
it, disconnect the heater from the electricity supply, undo the 4 screws in the
lid and remove it. Press the reset button (in front of the 8 way terminal
block) and refit the lid. Reconnect the heater to the electricity supply and
confirm it is working correctly.
THE SAFETY CUT OUT SHOULD ONLY BE RESET BY A COMPETENT PERSON.
Electrical Connection
The VBX30 is fitted with a 400V 5 pin (3P+N+E) 63A plug conforming to BS
EN60309. If required this plug may be replaced with a 400V 4 pin (3P+E)
63A plug.
THE PLUG SHOULD ONLY BE REPLACED BY A COMPETENT PERSON, UPON
COMPLETION EARTH CONTINUITY AND INSULATION RESISTANCE TESTS
SHOULD BE CARRIED OUT.
WARNING: THIS APPLIANCE MUST BE EARTHED.
Operation
The VBX30 has 4 power steps: Off- 10Kw – 20 Kw or 30Kw set by the right
hand knob.
The required temperature is set between 5-40
º
C by the left hand knob.
The rocker switch on the right hand side of the heater controls the fan
speed and air flow, either 1900 or 2600 m
³
/h.
Maintenance
The VBX30 does not require regular maintenance, but we recommend the
fan and elements are regularly checked and cleaned if a heavy build up of
dust or dirt is observed.
Electrical safety testing
Your heater should be regularly tested for electrical safety. The duration
between tests will depend on the type of use and environment. DO NOT
FLASH (HIPOT) TEST THIS HEATER.