![W.E. Anderson WE20 Series Installation And Operating Instructions Manual Download Page 10](http://html.mh-extra.com/html/w-e-anderson/we20-series/we20-series_installation-and-operating-instructions-manual_3105876010.webp)
10
TD02 and MD02 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque
110 VAC
20 s
85%
85%
0.24 A
442 in-lb
220 VAC
20 s
85%
85%
0.16 A
442 in-lb
24 VAC
20 s
85%
85%
1.28 A
442 in-lb
24 VDC
20 s
85%
-
1.28 A
442 in-lb
TD03 and MD03 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque
110 VAC
30 s
85%
85%
0.57 A
885 in-lb
220 VAC
30 s
85%
85%
0.35 A
885 in-lb
24 VAC
30 s
85%
85%
2.03 A
885 in-lb
24 VDC
30 s
85%
-
2.03 A
885 in-lb
TD04 and MD04 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque
110 VAC
30 s
85%
85%
0.65 A
1770 in-lb
220 VAC
30 s
85%
85%
0.37 A
1770 in-lb
24 VAC
30 s
85%
85%
3.57 A
1770 in-lb
24 VDC
30 s
85%
-
3.57 A
1770 in-lb
TD05 and MD05 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque
110 VAC
30 s
85%
85%
1.12 A
3540 in-lb
220 VAC
30 s
85%
85%
0.57 A
3540 in-lb
24 VAC
30 s
85%
85%
5.13 A
3540 in-lb
24 VDC
30 s
85%
-
5.13 A
3540 in-lb
TD06 and MD06 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque
110 VAC
45 s
85%
85%
1.18 A
5210 in-lb
220 VAC
45 s
85%
85%
0.60 A
5210 in-lb
24 VAC
45 s
85%
85%
6.04 A
5210 in-lb
24 VDC
45 s
85%
-
6.04 A
5210 in-lb
TD07 and MD07 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle
Full Load AMP Draw
Torque (in-lb)
110 VAC
30 s
85%
1.24 A
8850
220 VAC
30 s
85%
0.75 A
8850
24 VAC
30 s
85%
6.55 A
8850
24 VDC
30 s
85%
6.55 A
8850
TH03 and MH03
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
5 s
10 s
25%
75%
0.38
300
220 VAC
5 s
10 s
25%
75%
0.18
300
24 VAC
5 s
5 s
25%
75%
0.7
300
24 VDC
5 s
5 s
25%
75%
0.7
300
TH04 and MH04
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
10 s
20 s
25%
75%
0.38
400
220 VAC
10 s
20 s
25%
75%
0.18
400
24 VAC
10 s
10 s
25%
75%
0.9
400
24 VDC
10 s
10 s
25%
75%
0.9
400
TH05 and MH05
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
15 s
30 s
25%
75%
0.38
675
220 VAC
15 s
30 s
25%
75%
0.18
675
24 VAC
15 s
15 s
25%
75%
0.7
675
24 VDC
15 s
15 s
25%
75%
0.7
675
TH06 and MH06
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
15 s
30 s
25%
75%
0.38
1000
220 VAC
15 s
30 s
25%
75%
0.18
1000
24 VAC
15 s
15 s
25%
75%
1.1
1000
24 VDC
15 s
15 s
25%
75%
1.1
1000
TH08 and MH08
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
12 s
24 s
100%
100%
1.6
2000
220 VAC
12 s
24 s
100%
100%
1.03
2000
24 VAC
12 s
12 s
100%
100%
3.7
2000
24 VDC
12 s
12 s
100%
100%
3.7
2000
TH07 and MH07
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
30 s
60 s
25%
75%
0.38
1500
220 VAC
30 s
60 s
25%
75%
0.18
1500
24 VAC
30 s
30 s
25%
75%
1.1
1500
24 VDC
30 s
30 s
25%
75%
1.1
1500
TH09 and MH09
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
14 s
28 s
100%
100%
1.6
3840
220 VAC
14 s
28 s
100%
100%
1.03
3840
24 VAC
14 s
14 s
100%
100%
5
3840
24 VDC
14 s
14 s
100%
100%
5
3840
TH10 and MH10
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
38 s
76 s
50%
50%
1.6
5000
220 VAC
38 s
76 s
50%
50%
1.03
5000
24 VAC
38 s
38 s
50%
50%
5
5000
24 VDC
38 s
38 s
50%
50%
5
5000
TH11 and MH11
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
43 s
86 s
50%
50%
1.6
7020
220 VAC
43 s
86 s
50%
50%
1.03
7020
24 VAC
43 s
43 s
50%
50%
5
7020
24 VDC
43 s
43 s
50%
50%
5
7020
Electric Actuators Performance Rating