VWR SCCP-19 Owner'S Manual Download Page 17

 

Part number 20047, Rev 0

 

17 

 

QUICK TROUBLESHOOTING GUIDE 

 

Check these items before calling for service 

PROBLEM: 

POSSIBLE CAUSE / SOULTIONS: 

Unit does not run 

 

Electrical circuit is not 110-120V 60Hz. 

 

The power cord is not plugged in. 

 

No power at electrical outlet. Check to make sure 
breaker is not tripped or fuse is not blown. Additionally, 
make sure unit is not plugged into a Ground Fault Circuit 
Interrupter (GFCI) type of outlet.  

Unit does not maintain at the 
proper temperature 

 

Check the room temperature.  We recommend the 
refrigerator or freezer should be placed in the air 
conditioned room between 65°F to 85°F.  If the room 
temp is too warm, the refrigerator or freezer may not be 
able to maintain the interior temp at proper range.   

 

Door is not closed properly. 

 

Amount of stored product is overloaded. 

 

Product replacements are pushed against rear wall or 
interrupted the proper refrigerator air circulation.  For 
the proper air circulation, place the products evenly on 
each shelf.  Do not push against the refrigerator’s rear or 
side walls. 

 

Evaporator is blocked by frost or ice.  Remove the 
products, unplug the refrigerator or freezer power, and 
allow the unit to defrost.  If the problem still exists, call 
for service.  

 

3

rd

 party thermometer is placed incorrectly. For proper 

temperature monitoring, the thermometer should be 
place in the middle of refrigerator. 

PLEASE NOTE

!  Prior to shipment, each refrigerator and freezer 

has been calibrated and tested at proper temperature range. 

Appliance runs too long 

 

Prolong door openings. 

 

Control set too cold. 

 

Room temperature is high which will make the unit work 
harder to keep cool.  

Temperature of external wall 
surface is warm 

 

The exterior walls can be as much as 30 degrees warmer 
than room temperature due to the embedded 
condenser coils. This is normal when the unit is 
operating.   

 

 

Summary of Contents for SCCP-19

Page 1: ...agent driver at time of delivery Make sure you get a signed copy Send a written request for an inspection to the carrier B Concealed Damage This type of damage may not be discovered until the unit is...

Page 2: ...MANUFACTURER S TECHNICAL SERVICE DEPARTMENT please have the unit s model and serial number ready as well as the problem description The model and serial number is located on the serial tag which can b...

Page 3: ...y receipt acknowledging the damage This has to happen at the time of delivery or it won t happen at all Keep a copy for your records and send another to the carrier s damage claims department along wi...

Page 4: ...t needed PLEASE NOTE Your refrigerator or freezer is designed as INDOOR USE and should be operated at air conditioned room temperature between 65 F to 85 F Remove the lower grill assembly from the fro...

Page 5: ...the plastic door stoppers see Image 4 5 and 6 CASTERS INSTALLATION It is important to ensure the casters are installed properly and securely in order to obtain the maximum strength and stability of th...

Page 6: ...on cord Be sure your unit is properly grounded Use the 3 prong plug provided into a 3 prong grounded outlet Only this method complies with national electrical codes local codes and ordinances Unless t...

Page 7: ...nd product temperatures inside of the units and require no further adjustment Please contact the manufacturer s Technical Support Department before making any adjustment to make sure the adjustment is...

Page 8: ...king the evaporator fan s if installed There should be at least 4 inches of clearance below the fan s to allow proper air flow Do not overload the unit Maximum suggested load is about 75 of chamber ca...

Page 9: ...ated with the alarm system i e delay times system status a battery backup which will maintain the alarm system for several hours after a power failure to allow for continued alarm and notification fun...

Page 10: ...pressed The MUTE PROGRAM button has three functions In Normal Run mode if the unit is beeping pressing the button will mute the beeper for a preset time Each time the button is pressed the mute time r...

Page 11: ...the BEEPER and ALARM LED will both activate Press the MUTE PROGRAM button to stop the beeper for a specified time changing the sound to short chirps When the temperature goes back within range and the...

Page 12: ...n a short period 5 Once the Monitor is in Programming mode each time the Mute button is pressed the display steps to the next parameter As the display steps to the next parameter the value of the prev...

Page 13: ...mote Alarm Relay is a single pole double throw SPDT relay that changes state switches with the loss of line power or with the presence of an alarm condition NOTE The relay is rated for pilot duty oper...

Page 14: ...of the unit A touch keypad allows the user to easily select the display units set point differential set point and heating or cooling mode Please Note The digital temperature controller has been fact...

Page 15: ...et point and S1 will be blinking Press the up and down keys to adjust to the desired setting S1 blinking Setpoint Temperature Press SET key again to access the differential mode The LCD will display t...

Page 16: ...y EP Appears when the probe is open shorted or sensing a temperature that is out of range Check to see if the sensed temperature is out of range If not check for probe damage by comparing it to a know...

Page 17: ...placements are pushed against rear wall or interrupted the proper refrigerator air circulation For the proper air circulation place the products evenly on each shelf Do not push against the refrigerat...

Page 18: ...prevent leakage Door will not close The unit is not level Refer to the Leveling section at the beginning of this manual Check for dirt and debris or items passing through the door seal MOISTURE DURIN...

Page 19: ...sehold cleaners ammonia or alcohol to clean handles Use a soft cloth to clean smooth handles Do not use a dry cloth to clean smooth handles For Glass Door Units clean the glass with a mild detergent a...

Page 20: ...th pressurized air CO2 or nitrogen REMEMBER THE CLEANING OF THE CONDENSER IS NOT COVERED BY THE WARRANTY AND IS YOUR RESPONSIBILITY ANY DAMAGE CAUSED BY FAILURE TO KEEP THE CONDENSER CLEAN IS ALSO NOT...

Page 21: ...Y In addition to the two 2 year warranty stated above Horizon Scientific Inc warrants its hermetically and semi hermetically sealed compressors to be free from defects in both material and workmanship...

Page 22: ...od or other external causes It does not apply to defects resulting from failure to properly install operate or maintain the product in accordance with the printed instructions provided or damage cause...

Reviews: