VWR Flow Through Operator'S Manual Download Page 7

 

Section 3 - Troubleshooting 

3.1 Required 

Maintenance 

The refrigeration condenser fins are located just behind the front grill holes.  Dust that accumulates will 
reduce the amount of cooling power available.  The dust should be blown out with a compressed air 
hose.  All other items are permanently lubricated and need no attention. 
 

3.2 

Problem & Solution chart 

The following chart outlines a few problems that may arise.  The solutions are listed in order of priority. 
 

Problem

 

Solution

 

Does not run 

12, 4 

No cooling 

6, 7, 1, 2, 4, 10, 8 

Insufficient cooling power 

3, 5, 7, 6, 10, 2, 4, 11, 8 

Runs 5 minutes compressor shakes or stalls. Restarts 5 minutes later 

5, 2, 1, 8, 4 

Compressor will not start Clicks about every 30 seconds 

1, 2, 4, 8 

Gradual loss of cooling 

3, 10, 11 

Condenser fan not running or making loud noises 

Fluid gets too cold 

Stops cooling when fluid is cold 

6, 7, 5, 10, 11 

 
 
1. 

Compressor may be cycling on overload.  Shut off power for at least 10 min, then restart. 

 
2. 

Improper line voltage, frequency, or both.  Insufficient power supply during starting.  Check 
voltage at power source during start cycle.  Voltage must be within 10% of rated voltage.  Avoid 
extension cords that can cause voltage drops, 

 
3. 

See Sect. 3.1, Required Maintenance.  Check for airflow exiting the back of the unit.  Air vents 
should not be closer than 3 in. from a wall, or unit placed inside a cabinet.  Place where exiting 
warm air will not return to the intake or near warm air from other sources.  High room 
temperature reduces Cooler's capacity. 

 
4. 

Unplug unit, remove cover.  Check that condenser fan blade moves freely.  If not, check fan 
bracket or blade for misalignment. 

 
5. 

Fluid too hot for the Cooler to continuously cool.  Check specifications for heat removal.  At less 
than O

°

C, heat loss to the room may be excessive.  Containers and tubing should be insulated 

where condensation or frost occur.  High power pumps can introduce excessive heating. 

 
6. 

Fluid viscosity too high or freezing at desired temperature.  Flow-Through units may freeze 
internally and block the flow.  Freezing point of fluid should be 10

°

C to 20

°

C lower than desired 

temperature.  See Sect. 2.3, Choice of Fluids. 

 
7. 

Insufficient fluid flow rate to provide cooling.  Quick connectors or tubing less than 3/8 inch 
diameter on Flow-Through models may restrict flow.  Flow should be 3 to 15 liters/min. 

 
8. 

Compressor may be overcharged with refrigerant.  If compressor does not start and all other 
possibilities checked, compressor may be defective. 

 

Summary of Contents for Flow Through

Page 1: ...Operator Manual Flow Through Coolers Immersion Coolers 110 064 Rev C 05 03...

Page 2: ...ng Procedure For Immersion Coolers 2 5 Operating Procedure For Flow Through Coolers 2 6 Application Notes Section 3 Trouble Shooting 3 1 Required Maintenance 3 2 Problem Solution chart Section 4 Servi...

Page 3: ...r other causes not arising out of defects in material or workmanship There are no warranties expressed or implied including but not limited to those of merchantability or fitness for a particular purp...

Page 4: ...ith a copper tube within a tube heat exchanger The fluid to be cooled is circulated through the space between the tubes while the refrigerant evaporates to produce cooling inside the inner tube The fl...

Page 5: ...and wait 10 minutes before restarting 2 3 Choice of Fluids In order to select a fluid for low temperature use the viscosity of a fluid at low temperatures as well as its freezing point must be consid...

Page 6: ...r pump 5 Set the circulator s temperature control to the desired temperature When the temperature stabilizes the circulator s heater should cycle to maintain the set temp 6 Turn the Cooler s power swi...

Page 7: ...ltage Avoid extension cords that can cause voltage drops 3 See Sect 3 1 Required Maintenance Check for airflow exiting the back of the unit Air vents should not be closer than 3 in from a wall or unit...

Page 8: ...ssor valves may produce high pitch buzzing sound 12 Check power Unit s power switch should be illuminated Section 4 Service and Technical Support If you have followed the troubleshooting steps and you...

Reviews: