VSX SERIES STEAMER - ELECTRICAL OPERATION
Page 30 of 80
ELECTRICAL OPERATION
WATER LEVEL CONTROLS
Solid State -
Low level Cut-Off & Differential Control
The steamer is equipped with three water level
sensing probes (high, low and low level cut-off) and
a single water level control board. The water level
control board performs two functions: 1) Provide low
level cut-off protection to shut off the heat source in
case the water level drops below the low level cut-
off (LLCO) probe. 2) Perform as a differential level
control to maintain the water level between the low
and high water level probes.
The water level control (WLC) has input voltage
(120VAC) across terminals 11 and 12 which powers
the primary side of the transformer. On one side of
the transformer secondary, power is provided to the
control by a series path through chassis ground
(terminal 10). The other side of the transformer
secondary (12VAC) is attached to the probe that
directs power to the other side of the internal relays
(LLCO, HL and ILR). As water enters the boiler, it
becomes part of the water level control’s circuit.
When the water level in the boiler reaches a probe,
that circuit is completed.
The inverse latching relay of the board is de-
energized, leaving the ILR-1 (N.O.) and ILR-2 (N.C.)
contacts in their shelf state.
When the main power switch is turned ON, power is
supplied to the WLC board which energizes the high
level (HL) relay and illuminates the HL relay LED.
With the HL-3 contacts closed, the boiler fill
solenoid is energized and water begins filling the
boiler.
When the water level reaches the low level cut-off
(LLCO) probe, the LLCO relay is energized and
illuminates the LLCO LED. With the LLCO-2
contacts closed the heat source is then energized.
The LLCO relay will remain energized and its LED
will stay lit until the water level in the boiler drops
below the LLCO probe.
When the water level reaches the low level (LL)
probe, power to terminal 2 on the WLC board is
present but no switching occurs.
After the water level reaches the high level (HL)
probe, the inverse latching relay of the board is
energized and locked through the low level probe
(LL) and ILR-1 contacts. With ILR-2 contacts open,
this de-energizes the HL relay and the HL LED goes
out. With the HL-3 contacts open, the boiler fill
solenoid is de-energized, stopping the flow of water
into the boiler.
When the water level drops below the low level (LL)
probe, power is removed from the inverse latching
relay, the HL relay energizes through ILR-2 and HL
contacts change state. The fill solenoid is energized
through HL-3 to refill the boiler and the HL LED is lit.
The HL relay and LED will toggle ON and OFF
during a cooking cycle as needed.
Summary of Contents for VSX24D
Page 12: ...VSX SERIES STEAMERS COMPONENT FUNCTION AND LOCATION Page 12 of 80 ...
Page 13: ...VSX SERIES STEAMERS COMPONENT FUNCTION AND LOCATION Page 13 of 80 ...
Page 40: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 40 of 80 PAGE PURPOSELY LEFT BLANK ...
Page 42: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 42 of 80 Electronic Ignition Standard Controls ...
Page 43: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 43 of 80 Manual Ignition CSD 1 Code Controls ...
Page 44: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 44 of 80 Electronic Ignition CSD 1 Code Controls ...
Page 45: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 45 of 80 ...
Page 47: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 47 of 80 ...
Page 48: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 48 of 80 Electronic Ignition Standard Controls ...
Page 49: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 49 of 80 ...
Page 50: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 50 of 80 Manual Ignition CSD 1 Code Controls ...
Page 51: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 51 of 80 ...
Page 52: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 52 of 80 Electronic Ignition CSD 1 Code Controls ...
Page 53: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 53 of 80 ...
Page 55: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 55 of 80 Auto Blowdown Cal Code Controls ...
Page 56: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 56 of 80 Auto Blowdown Standard Controls ...
Page 57: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 57 of 80 Auto Blowdown Cal Code Controls ...
Page 59: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 59 of 80 ...
Page 60: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 60 of 80 Auto Blowdown Cal Code Controls ...
Page 61: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 61 of 80 ...
Page 62: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 62 of 80 Auto Blowdown Standard Controls ...
Page 63: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 63 of 80 ...
Page 65: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 65 of 80 ...
Page 67: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 67 of 80 ...
Page 69: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 69 of 80 ...
Page 72: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 72 of 80 3 Phase 4 Wire Older Models ...
Page 75: ...VSX SERIES STEAMER ELECTRICAL OPERATION Page 75 of 80 Auto Blowdown ...