background image

 

VTS reserves the right to implement changes without prior notice

 

 

VENTUS S-Type Air Handling Units

 

 
 

The measurement should be carried out at the duct's fragment with parallel walls and straight segments at 
least 6 times longer than the duct diameter or equivalent diameters before the test point and not less than 3 
diameters after it. In the real ventilation system finding such a long straight fragment can be a problem. In such 
a case determine the measurement cross-section in a place where the smallest distortions of the air-flow are 
expected and intensify a network of test points. The location of the measurement cross-section should be 
determined on the system design stage. Detailed recommendations concerning the air-flow measurement and 
the location of the test points are defined by the ISO 5221 standard.

 

 

We estimate the output is considered to be sufficient unless it differs more than ±10% from the 
recommended one. In case of bigger disproportions, the output matching the recommended one can be 
achieved by:

 

- an adjustment of the ventilation ducts network,

 

- changing the adjustment of the main damper,

 

- changing the fan rotary speed.

 

While increasing the fan's rotary speed you must by all means control the motor's power consumption and not 
allow to exceed the recommended rated current value. For durability and permissible operation parameters it is 
also very important not to exceed the maximal rotor speed. In justified situations, when there is a need to 
increase the air-flow output, it is recommended to use a more powerful fan's motor.

 

 

In systems equipped with dampers which automatically change the ratio of fresh, recycled and exhausted air or 
the by-pass flow ratio, output measurements and the main damper adjustment should be carried out in the end 
setting position. Next check the air ratio and the overall output in the other end position and, if necessary, carry 
out appropriate adjustments in order to the achieve proper ration at constant overall output.

 

 

6.1. Cooler performance adjustment

 

Adjustment of the cooler performance should be carried out in conditions similar to the rated ones.

 

 

The temperature of the cooling agent is controlled in this way as well. If the cooler operation effect is not 
satisfactory, an appropriate adjustment is required. It can be carried out using the following methods:

 

- an adjustment of the cooling medium amount (water coolers),

 

- an adjustment of the air amount passing through the AHU (water cooler),

 

 

Coolers operate in most cases in complex air-conditioning systems equipped with an automatic control. 

Automatic control devices should be tested not only in extreme conditions but also in intermediate cooler load 
circumstances.

 

 

7. OPERATION AND MAINTENANCE

 

 

Personnel in charge of AHU operation should read through this documentation before starting 
any operation and maintenance activities. When no such personnel with appropriate skills and 
competence is available, periodic inspections should be carried out by the authorized VTS 
service providers.

 

EN 

Any damages of the AHU or its parts resulting from not following the guidelines stated in this 
documentation will not be subject to warranty claims.

 

 

Basic AHU technical data such as type, parameters and dimensions of the most significant parts are provided in 
the Technical Data Card supplied with each device.

 

 

Any AHU maintenance operations should be carried out with the device turned off.

 

In order to ensure safe device operation, a service switch cutting off power supply to the motor 
during service operation must be installed outside the fan section. Switching off the power circuit 
with the service switch must be done in the non-voltage state. The service switch should be 
located close to the inspection panels of the fan section.

 

Thorough and regular maintenance, as well as technical inspections of the AHU and its components, are 
necessary in order to detect the failures at an early stage - before more serious damages appear.

 

This documentation includes only general guidelines regarding control periods, which ensure error-free operation 
of the AHU due to various possible external conditions. Control periods must be adjusted to the local conditions 
(contamination, number of start-up cycles, load, etc.). 

 

 

18 

Summary of Contents for Ventus S Series

Page 1: ...VENTUS S Type Air Handling Units Operation and Maintenance Manual OMM SVS ver 2 0 03 2019...

Page 2: ...t prior notice VENTUS S Type Air Handling Units EN ATTENTION In order to ensure proper condensate elimination this Air Handling Unit requires accurate levelling Use a spirit level tool when installing...

Page 3: ...s 10 4 4 Draining out condensate 11 4 5 Electric connection 12 4 6 Fan sets 12 4 7 Automatic control 15 5 PREPARATION FOR START UP 16 5 1 Electrical system 16 5 2 Filters 16 5 3 Fan unit 16 6 START UP...

Page 4: ...cumentation and any other materials provided with the unit contain information designed for the qualified technical personnel Connection of the AHU to related systems start up operation and maintenanc...

Page 5: ...x h outlet w1 x h1 SVS 35 1 120 1 160 530 98 106 342 x 264 1100 x 470 342 x 264 SVS 50 1 120 1 300 595 114 124 365 x 275 1240 x 535 365 x 275 SVS 70 1 120 2 000 530 166 181 1294 x 264 1940 x 470 1294...

Page 6: ...ive the units become a property of the customer Right after the unit is delivered check the condition of the package and examine if all necessary elements have been delivered in conformity with the at...

Page 7: ...vered by the guarantee and any claims laid by way of the aforementioned issues will not be examined by VTS 4 MOUNTING CONNECTION TO UNIT RELATED SYSTEMS Connecting supplied SVS 35 100 units to the ins...

Page 8: ...AHU sections Fig 6 Suspension grips arrangement The space between the slings must allow for the assembly of the siphon if there are no the special pump which drains the condensate out of the unit On b...

Page 9: ...n of the duct and the AHU outlets Flexible connections are equipped with flanges and sealing The flexible flanges should be connect with ducts by drilling screws Fig 8a or additional clamping elements...

Page 10: ...e other AHU sections The way of connecting the exchangers with the supply system should allow for an easy pipeline disassembly in order to remove the exchanger from the AHU during maintenance and serv...

Page 11: ...d as a standard delivery Siphon s usable H height depends on the pressure difference between the AHU section where the condensate is drained during the operation and under the ambient pressure H dimen...

Page 12: ...ion are required Table 4 Technical data of fan sets Unit Size FAN Model AC Motor Rated Output Poles Efficiency Class Protection Grade Rated Current at 415V 3ph 50Hz 230V 1ph 50Hz 380V 3ph 50Hz 400V 3p...

Page 13: ...ng powering the motor can generate some electromagnetic interferences The connection between the frequency converter and motor should be using shielded cables in accordance with guidelines outlined in...

Page 14: ...es without prior notice VENTUS S Type Air Handling Units Fig 12b Connecting diagram of the AC in SVS 70 100 1 without frequency converter 2 with frequency converter Fig 12c Connecting diagram of the E...

Page 15: ...ce In many cases it is an indispensable element and the lack of it may lead to serious operational problems or failures This documentation does not include information regarding the assembly of automa...

Page 16: ...e no loose or redundant cables left 5 2 Filters Air filters in AHU prevent dust from getting into ventilated rooms Additional they protect other AHU functional elements e g water exchangers against co...

Page 17: ...required performance of the AHU depends among other factors on the adjustment to the recommendations and the test measurements 6 1 Measurement of the air quantity and AHU output adjustment Measurement...

Page 18: ...tment Adjustment of the cooler performance should be carried out in conditions similar to the rated ones The temperature of the cooling agent is controlled in this way as well If the cooler operation...

Page 19: ...ng the parts please use the type and factory identification number of the device This information can be found on the rating plate located on the fan section 7 1 Dampers If the damper is contaminated...

Page 20: ...lead to the damage of bearings corrosion unbalanced rotor or vibrations The fan and motor in the unit have been designed for particular requirements and operation characteristics Fan rotation speed is...

Page 21: ...ce personnel is always available to accompany you during the start up maintenance and in case of any emergency related to the device operation VTS Authorized Service Providers sell spare parts and acc...

Reviews: