MB_ADDR_ZONE_PROGRAM - a variable that allows to set a operating mode of the device.
Acceptable values for the variable:
Variable
value
Operating mode
Descritpion
0
Continuous
Constant (not time-limited) control of room atmosphere
1
Schedule
Environment control in rooms dependent on schedule (see from MB ADDR
ZONE
SCHEDULE
MON
FRI
WORK
1
START
to. MB_ADDR_ZONE_SCHEDULE_SUN_WORK_2_STOP).
Table 18. Operating mode
Attempt to record a number beyond the allowable values leads to an error message. The variable is stored in
backed-up EEPROM memory.
.
MB_ADDR_ZONE_MODE_CONDITION - a variable that allows to set operating conditions of the
device. Acceptable values for the variable:
Variable
value
Operating
condition
Work characteristics
Door status
Temperature
Heater
Fan
0
Door
Open
T
ACT
> T
TAR
OFF
ON
T
ACT
< T
TAR
ON
ON
Closed
T
ACT
> T
TAR
OFF
OFF
T
ACT
< T
TAR
OFF
OFF
1
Room
n/a
T
ACT
> T
TAR
OFF
OFF
T
ACT
< T
TAR
ON
ON
2
Door and room
Open
T
ACT
> T
TAR
OFF
ON
T
ACT
< T
TAR
ON
ON
closed
T
ACT
> T
TAR
OFF
OFF
T
ACT
< T
TAR
ON
ON
T
A
CT
- Current temperature of a room in which the device is located
T
TAR
– target (set) temperature
Table 19. Operating conditions.
Attempt to record a number beyond the allowable values leads to an error message. The variable is stored in
backed-up EEPROM memory.
MB ADDR ZONE MODE - a variable that allows to determine a current device operating condition.
Allowable values for the variable:
13