Table I/O (for application ver. to 1.0.005)
UPC3
UPC3
Supply
Analog Inputs
G
+24V DC
B1
Temp. Supply
G0
-24V DC
B2
Temp. Return (Room) / PreHeater (for Compact AHU)
Digital Inputs
B3
Temp. External
DI1
Fire Alarm
B4
Temp. Exhaust
DI2
Heater Alarm / DXH Alarm
B5
Temp. Water Heater
DI3
Cooler Alarm / DXH Alarm
B6
Temp. Recovery on Supply / PreHeater (for Ventus AHU)
DI4
Humidity Alarm / Filter supply alarm
Analog Outputs
DI5
DX_H reverse / Filter return alarm
Y1
Recovery / Mixing damper / Heater / Re-Heater for DX_H
DI6
Remote STOP
Y3
Recovery / Mixing damper / Cooler / DX_H
Relay Outputs
Communication
NO1
Heater / Re-Heater for DX_H
Ethernet RJ-45
Web Visualization / Modbus TCP/IP (external)
NO2
Dampers
RS-485
Modbus RTU Master (internal)
NO3
Global Alarm / ReHeater / PreHeater
pLan
HMI Advanced – pGD1
NO4
Cooler / DX_H
NO5
Cooler 2 / Humidifier / Glycol / Redundant / DX_H reverse
NO6
Heater 2 / DX_H st. 2 / Humidifier
PCB EC
PCB EC
Supply
Digital Inputs
24V
+24V DC
IN1
Supply Filter alarm
24V
-24V DC
IN2
Return Filter alarm
Analog Outputs
Communication
AO1 -
AIN
10V
Recovery / Humidifier
RS-485
Modbus RTU Slave (internal)
AO2-
AOUT
0-10V
Recovery / Mixing dampers / Re-Heater / Pre-Heater
Summary of Contents for 3x400V 1x1VFD 11kW
Page 15: ...EN VTS reserves the right to implement changes without prior notice 15...
Page 17: ...EN VTS reserves the right to implement changes without prior notice 17...
Page 19: ...EN VTS reserves the right to implement changes without prior notice 19...
Page 21: ...EN VTS reserves the right to implement changes without prior notice 21...
Page 23: ...EN VTS reserves the right to implement changes without prior notice 23...
Page 26: ...EN VTS reserves the right to implement changes without prior notice 26...