SF-PB & SF-PC QUICK SETUP GUIDE

SERIES 1000-X CONTROL PACK

SERIES 1000-X CONTROL PACK

DOC-00000326(D) - 1

The SF-PB or SF-PC control pack, when shipped together with a Series 1000-X actuator, 

is factory calibrated and set for 90° rotation; 

NO ADJUSTMENT IS NECESSARY

. If you are 

replacing an SF-PB or SF-PC setting of the position limits is 

MANDATORY

 before use. 

NOTE: ACTUATOR IS EQUIPPED WITH MECHANICAL STOPS.  THESE ARE FOR MANUAL OPERATION 

ONLY AND SHOULD NOT BE USED TO SET THE POSITION LIMITS ON THE ACTUATOR. 

INITIAL SETUP

If not connected to the actuator, install the SF-PB or SF-PC by plugging the three cables from the 

actuator into the unit. Connect the appropriate power to terminals 1&2. Connect the control signal to 

terminals 3&4. The control signal is polarity sensitive and 

must be correctly connected positive (+) 

and negative (-).

If feedback is being used, connect the wiring to terminals 5&6. The SF-PB and SF-PC provides 

position feedback of 4-20mA. If 2-10Vdc feedback is required apply a 500 ohm resistor in parallel 

across terminals 5&6.

At this point, the Green LED “L1” should be illuminated.  If Red LED “L2” is illuminated then the 

control signal is faulty or SC switch in Figure B above is not set correctly for your control signal.  

Ensure the SC switch is set for your input control signal (2-10V or 4-20mA).  Once there are no Red 

LED’s illuminated, your actuator is ready to operate. Increase/decrease your control signal to confirm 

proper operation. See the chart below for failure mode conditions on the SF-PB control pack. 

SF-PB AND SF-PC CONTROL PACK LED’S

LED

CAUSE DESCRIPTION

REMEDY

LED-1 (GREEN)

POWER IS PRESENT ON INPUT TERMINALS

NORMAL OPERATION

LED-2 (RED)

IMPROPER CONTROL SIGNAL, NOT PRESENT OR INCORRECT 

POLARITY

CHECK SC SWITCH TO ENSURE PROPER CONTROL 

SIGNAL(2-10v/4-20mA) - CHECK TO ENSURE SIGNAL IS 

PRESENT

LED-3 (RED)

POTENTIOMETER IS NOT CALIBRATED WITH ACTUATOR

MANUALLY MOVE ACTUATOR TO MID POSITION THEN 

RETURN TO SERVICE. (CALL FOR ASSISTANCE IF PERSISTS)

LED-4 (RED)

OVER-TORQUE CONDITION PRESENT - VALVE BINDING, OR 

MANUAL OVERRIDE HAS BEEN USED AND ACTUATOR IS OUT OF 

SYNC WITH CONTROLLER

CHECK TO MAKE SURE VALVE IS NOT BINDING. RESET 

CONTROL PACK BY ROTATING SA FROM 1 TO 2 AND BACK TO 

1, OR REMOVE/REPLACE POWER TO THE UNIT

NOTE: THE ACTUATOR WILL NOT OPERATE UNLESS THE AUTO/MANUAL OVERRIDE PUSH BUTTON IS DEPRESSED.

FIGURE A

FIGURE B

LED 1

LED 2

LED 3

LED 4

SC

OPEN

SHUT

SET

SA SB

DB

POWER CTRL

FEED

BACK

+

+

+

-

-

-

     

     

!