VSL2.909.031ASY
V1.04
Fig.2
Terminal Connection
1.
1,3:
connecting with Detection loop L+;L-(Input),
A side isolate.
2.
8,10:
connecting with Detection loop L+;L-
(Output),B side isolate.
3.Loop wiring is shown in Fig.3
Warning
Maxmium 32 devices connect with one side of Isolate
Interface.
Please make sure 1,10 connect with L+;3,8 connect
With L-.It recommends using different colors to distinguish
the line.Otherwise it will cause the loop wiring error.
Fig.3
Wiring Guide
Wiring guide in Fig.4.
If short circuit at “Zone 1”,
“ Active B” LED of
Isolate
Interface A
and “ Active A”
LED of
Isolate Interface B
will emitting ,“Detection
Zone 1” will be isolated.
If “Zone 3 ” had short circuit
fault,the
Isolate interface C
will start to isolate, “Active
B”of Isolate Interface C will
emitting. And A side of
Isolate Interface D
also start
to isolate.
Testing
Warning
:
Power is switched on after all devices are installed completely.
Isolate test:
The LED indicator “Active A” or “Active B” will emitting when apply the short circuit to
corresponding side of isolate Interface.
Reset:
Remove the short circuit fault,the the isolate interface will go back to normal.
Mounting direction
Fig.4