VSAIL VI-6627 Installation And Operation Manual Download Page 2

 

 

VSL2.909.026ASY                                                                                           

                         

  V1.01

 

 

 

Mounting: 

Warning:  Please  disconnect the  loop power  in  order  to  avoid control panel  broken by short  circuit when 
mounting Common Base. 

Detector Head Mounting showing in Fig.2 
 

 

 

Fig.2 Mounting 

 

Mounting Step 

1.Install the Common Base into Back Box which had installed in the wall by using screw.( Back box is standard 
86H50 box)Make sure the Common Base installed stable. 
2.Connect the loop to Common Base Terminal 1,2. 
3.Inastall the detector head on to Common Base and direct Alignment Mark to Mounting Mark at same time. 
4.Turn Alignment Mark aim to Locking Mark finish the installation. 

Wiring Details 

1. Wiring Requirement:RVS-2*1.0 mm2 or1.5 mm2 wire for BUS, laid through metal tube (cable sink) or PVC tube.
2.1,2 Should connecting with fire alarm system detection loop(Non-polarized) 
3.Loop wiring is shown in Fig.3 
 
 
 
 
 
 
 
 
 
 
 

Fig.3. Loop wiring 

 

Address setting 

1.VI-6537 Digital Programmer is used to write an address of the Detector.Connecting Progarmmer with loop 
terminals:1,2 of the Detector before it installation . 
2.Set address ,Pressing Write key, the address will be shown on the numeric display if successful. It is fail if there 
is no address. Please refer to VI-6537 Digital Programmer Manual for details. 
3.Address range should be within 0

255. The address is unique in a loop. 

Back Box 

Alignment Mark 

Mounting Mark 

Locking Mark 

L+             

L- 

Loop(Non-polarized) 