Assembly and Safety Information
Installation must be carried out under observation of the relevant
regulations and standards. Installation must be carried out in a
voltage-free state (i.e. disconnection from the mains). The following
advices must be observed; non-observance can result in the
destruction of the LED drivers, fire and/or other hazards.
Mandatory regulations
• DIN VDE 0100
• EN 60598-1
Mechanical mounting
• Mounting position: Built-in: Any position inside a luminaire
is
allowed
• Mounting location: LED drivers are designed for integration into
luminaires or comparable devices.
Installation in outdoor luminaires: degree of
protection for luminaire with water protection
rate
≥
4 (e.g. IP54 required).
• Degree of protection: IP20
• Clearance:
Min. 0.10 m from walls. ceilings and
insulation
• Surface:
Solid and plane surface for optimum
heat dissipation required.
• Heat transfer:
If the driver is destined for installation in a
luminaire. sufficient heat transfer must be
ensured between the driver and the luminaire
casing.
LED drivers should be mounted with the
greatest possible clearance to heat sources.
During operation. the temperature measure at
the driver's t
c
point must not exceed the
specified maximum value.
• Fastening:
Using M4 screws in the designated holes
• Tightening torque: 0.2 Nm
Electrical installation
• Connection
terminals:
Push-in terminals for rigid or flexible conductors
with a section of 0.2–1.5 mm²
• Stripped length:
8.5–9.5 mm
• Wiring:
The mains conductor within the luminaire must
be kept short (to reduce the induction of
interference).
Mains and lamp conductors must be kept
separate and if possible should not be laid
in parallel to one another.
• Polarity:
Please ensure the correct polarity of the leads
prior to commissioning. Reversed polarity can
destroy the modules.
• Through-wiring:
Is not allowed.
• Secondary load:
The sum of forward voltages of LED loads
has to be within the tolerances which are
mentioned in the table "Electrical Charac-
teristics" in this data sheet.
• Wiring diagram:
Selection of automatic cut-outs for VS LED drivers
• Dimensioning automatic cut-outs
High transient currents occur when an LED driver is switched on
because the capacitors have to load. Ignition of LED modules
occurs almost simultaneously. This also causes a simultaneous high
demand for power. These high currents when the system is switched
on put a strain on the automatic conductor cut-outs. which must be
selected and dimensioned to suit.
• Release reaction
The release reaction of the automatic conductor cut-outs comply
with VDE 0641. part 11. for B. C characteristics. The values shown
in the following tables are for guidance purposes only and are
subject to system-dependent change.
• No. of LED drivers
The maximum number of VS LED drivers applies to cases where the
devices are switched on simultaneously. Specifications apply to
single-pole fuses. The number of permissible drivers must be
reduced by 20% for multi-pole fuses. The considered circuit impe-
dance equals 400 m
Ω
(approx. 20 m [2.5 mm²] of conductor
from the power supply to the distributor and a further 15 m to the
luminaire).
Type
Ref. No.
Automatic cut-out type and
possible no. of VS drivers
pcs.
Automatic cut-out type B
B 10 A
B 13 A
B 16 A
ECXe 1050.357
186880
23
29
36
ECXe 1050.358
186881
18
23
28
ECXe 1050.359
186882
8
10
12
ECXe 1050.360
186883
7
9
11
Automatic cut-out type C
C 10 A
C 13 A
C 16 A
ECXe 1050.357
186880
37
48
59
ECXe 1050.358
186881
30
39
48
ECXe 1050.359
186882
13
17
21
ECXe 1050.360
186883
11
15
18
– To limit capacitive inrush currents the current carrying capacity of
each circuit breaker (fuse) can be increased by a factor of 2.5
with the help of our ESB (Ref. No.: 149820, 149821, 149822)
inrush current limiters.
EU compliance information
Hereby, Vossloh-Schwabe Deutschland GmbH declares that the radio
equipment type ComfortLine NFC/LEDSet S-MidNight is in complian-
ce with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the
following internet address: www.vossloh-schwabe.com.
LED Drivers – ComfortLine NFC/LEDSet S-MidNight