INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

MANUAL OPERATION 

PRECAUTIONS 

• Manual operation should be a temporary operation.   
• Be sure to turn off the power before manual operation. 
• Actuator may operate for 15 minutes after power 

shuts off for ECR-120, and 30 minutes for ECR-360. 
When manual operation is required, follow steps 
below. 

1)  Turn manual shaft slowly with a 

smooth-jawed wrench.   

2)  When limit switch leaves from SW setting 

cam, actuator's motor starts.   
Keep it in that position.   

3)  In about 30 seconds, motor protect circuit 

starts and the motor stops.   
Go ahead and operate manually.   

THE WAY OF OPERATION 

Turn manual shaft slowly with an adjustable wrench. 

Before automatic operation, be sure to remove 
wrench. 

MAINTENANCE 

• To prevent electric shock, be sure to turn off the power 

when removing the actuator cover.   

• Do the routine maintenance at least once in half a 

year.   

Inspection items 

• Confirm operation of opening and closing.   
• Confirm that an actuator is not hot excessively. 
• Confirm existence of abnormal noise and 

vibration during operation.   

• Confirm whether screws are loose or not.   
• Confirm that water or condensation no remains 

in the actuator.   

• Turn off the power and check if the valve 

operates normally with built-in capacitor. 

TROUBLE SHOOTING

Problem 

Cause 

Solution 

Actuator 
does not 
move. 

Faulty wiring.    Correct the wiring. 

 

No voltage is 
coming. 

Check the voltage. 

 

Incorrect 
voltage. 

When it's burned out by 
excess voltage, replace 
the actuator.   

 

Short the 
circuit, contact 
failure. 

Review wires and 
connection. 

 

Motor is too 
old.   

Replace the actuator. 
Repair in our factory. 

 

Capacitor is 
too old.   

Replace the capacitor. 

Operation is 
unstable. 

Excess surge 
or voltage was 
applied. 

• Replace the control 

board or limit switch. 
(Repair in our factory)

• Replace the actuator. 

 

Rainwater 
entered the 
actuator. 

• Dry the inside.   
• Replace the actuator. 

 

Added high 
harmonics 
noise from an 
inverter. 

Attachment a filter for 
each inverter maker 
option.   

 

Effect of high 
level noise. 

Use the shielded wire 
and ground the wiring.   
Separate signal wire 
from power line.   

 

Switch leakage 
current is 
large. 

Current leakage should 
be less than 1 mA.   

Stop in the 
mid position. 

Biting of valve 
seat. 

Manually operate an 
actuator and remove a 
foreign object. 

 

Overload 
protector runs 
because of 
over-torque.   

Motor protection circuit 
returns by the signal of 
operation of an 
opposite direction.   
Turn on the power 
again. 

Received 
the alarm 
signal.   

For more information contact   
NIPPON VALVE CONTROLS, INC. for consultation. 