VPFlowScope M
34
© 2016 Van Putten Instruments BV | MAN-VP-MPRO-UK | Revision:1602 | Date:20-10-2016
0115 - 0116
277 - 278
Totalizer positive m
3
n
32-bit integer Read
0117 - 0118
279 - 280
Totalizer negative m
3
n
32-bit integer Read
0119 - 011A
281 - 282
Totalizer MSCF
32-bit integer Read
011B - 011C 283 - 284
Totalizer positive MSCF
32-bit integer Read
011D - 011E 285 - 286
Totalizer negative MSCF
32-bit integer Read
Alarm
012C - 012C 300 - 300
Alarm mode
16-bit integer Read / write
012D - 012D 301 - 301
Alarm hold period
16-bit integer Read / write
012E - 012E 302 - 302
Alarm reset period
16-bit integer Read / write
012F - 012F
303 - 303
Alarm unit
16-bit integer Read / write
0130 - 0131
304 - 305
Alarm counter
32-bit integer Read
0136 - 0137
310 - 311
Alarm low boundary *
Floating point Read / write
0138 - 0139
312 - 313
Alarm high boundary *
Floating point Read / write
Configuration registers
03E8 - 03E8 1000 - 1000 Totalizer reset all
Write
03E9 - 03E9 1001 - 1001 Alarm counter reset
Write
041A - 041B 1050 - 1051 4..20mA zero *
Floating point Read / write
041C - 041D 1052 - 1053 4..20mA span *
Floating point Read / write
041E - 041F
1054 - 1055 Pulse size m
3
n
*
Floating point Read / write
0420 - 0421
1056 - 1057 Pulse size SCF *
Floating point Read / write
0422 - 0422
1058 - 1058 4..20mA unit
16-bit integer Read / write
0423 - 0423
1059 - 1059 I-out mode
16-bit integer Read / write
044C - 044D 1100 - 1101 Diameter mm *
Floating point Read / write
044E - 044F
1102 - 1103 Diameter inch *
Floating point Read / write
04B0 - 04B0 1200 - 1200 Modbus address
16-bit integer Read / write
04B1 - 04B1 1201 - 1201 Modbus multiplier
16-bit integer Read / write
* Value will only change if both registers are written
VPSensorCartridge connection status
Modbus return value
Description
0
No VPSensorCartridge connected
1
VPSensorCartridge is connected
2
VPSensorCartridge is connected but not powered
3
VPSensorCartridge error, see error code and contact local distributor