--4--
Selection of the selector switches, the switching voltages
and of the operating mode:
Six (6) selector switches are located at the unit rear. Move the white levers vertically to the desired position:
Switches
1 and 2:
for optionally
3 fixed switching thresholds
or
automatic switching threshold
(lead)
Switch
3:
Board Supply Voltage:
12 V ( X
)
or
24 V ( - )
Switch
4:
Audible Alarm
(Beep) desired
:
ON ( X )
or
OFF ( - )
Switch
5:
Not assigned, always in position ( - )
Switch
6:
Sensor Line “”
(Option)
:
ON ( - )
or
OFF ( X )
see page 3
Figure shows the
factory-adjustment
of the switches:
1 and 2:
Disconnection Voltage: Automatic Switching Threshold
1 and 2:
Connection Voltage:
12.5 V
3
Board Supply Voltage: 12 V
4
Audible Alarm:
active
5
Not used:
always (-)
6
Sensor Line:
Operation without
sensor line
Table Selector Switches
3
,
2
and
1
:
Selectable switching thresholds with delay times or automatic switching threshold:
3 2 1
Disconnection Voltage
24 V
Connection Voltage
-
-
-
21.2 V / 40 s
24.8 V / 1 s
-
-
x
23.0 V / 40 s
25.0 V / 1 s
-
x
-
23.6 V / 40 s*
25.6 V / 1 s*
-
x
x
Automatic
25.0 V / 2 s
3 2 1
Disconnection Voltage
12 V
Connection Voltage
x
-
-
10.6 V / 40 s
12.4 V / 1 s
x
-
x
11.5 V / 40 s
++
12.5 V / 1 s
++
x
x
-
11.8 V / 40 s *
+
12.8 V / 1 s *
+
x
x
x
Automatic
12.5 V / 2 s
The unit can extend the lifetime of Lithium LiFePO4 batteries, if it had been set in such a way, that it
switches off before the BMS safety system against low voltage of the battery acts.
For
lithium batteries
, the unit is
not suitable
as substitute
for a
BMS
safety system of the battery!
++
Lithium LiFePO4 batteries, recommended for high load
+
Lithium LiFePO4 batteries, recommended for low or moderate load
*
Switching thresholds according to DIN EN 1789, starter batteries: Warning the driver of a battery,
which is not capable to start (such as for intervention vehicles with only one battery circuit) and of the
disconnection of additional consumer loads at this battery circuit.