--4-- 

Selection of the selector switches, the switching voltages  

and of the operating mode: 

 

 

Six (6) selector switches are located at the unit rear. Move the white levers vertically to the desired position:  

 

Switches

 1 and 2: 

for optionally 

3 fixed switching thresholds 

or 

automatic switching threshold 

(lead)

 

Switch

 3: 

Board Supply Voltage:    

12 V  ( X

 

)   

or 

  24 V  ( - ) 

Switch

 4: 

Audible Alarm 

(Beep) desired

ON    ( X )   

or

   OFF   ( - ) 

Switch

 5: 

Not assigned, always in position ( - )

  

Switch

 6: 

Sensor Line “” 

(Option)

ON    ( - )    

or

   OFF  ( X )    

see page 3

 

 

Figure shows the 

factory-adjustment 

of the switches:

 

 

1 and 2: 

Disconnection Voltage:  Automatic Switching Threshold 

1 and 2: 

Connection Voltage: 

12.5 V 

3   

Board Supply Voltage:  12 V   

4   

Audible Alarm: 

active 

5   

Not used: 

always (-) 

6   

Sensor Line: 

Operation without  

 

 

sensor line 

 

 

 

 

 

 

Table Selector Switches   

3

,  

2

  

and  

1

:  

 

Selectable switching thresholds with delay times or automatic switching threshold: 

 

3             2             1 

Disconnection Voltage   

24 V

 

 Connection Voltage  

21.2 V / 40 s 

24.8 V / 1 s 

23.0 V / 40 s 

25.0 V / 1 s 

23.6 V / 40 s* 

25.6 V / 1 s* 

Automatic 

25.0 V / 2 s 

3             2             1 

Disconnection Voltage   

12 V

 

 Connection Voltage  

10.6 V / 40 s 

12.4 V / 1 s 

11.5 V / 40 s 

++

 

12.5 V / 1 s 

++

 

11.8 V / 40 s *  

+

 

12.8 V / 1 s *  

+

  

Automatic 

12.5 V / 2 s 

 

The unit can extend the lifetime of Lithium LiFePO4 batteries, if it had been set in such a way, that it 

switches off before the BMS safety system against low voltage of the battery acts.  
For 

lithium batteries

, the unit is 

not suitable

 

as substitute 

for a  

BMS

 safety system of the battery! 

 

++

  

 Lithium LiFePO4 batteries, recommended for high load

 

   

+

  

 Lithium LiFePO4 batteries, recommended for low or moderate load

 

 *  

Switching thresholds according to DIN EN 1789, starter batteries:  Warning the driver of a battery, 

which is not capable to start (such as for intervention vehicles with only one battery circuit) and of the 

disconnection of additional consumer loads at this battery circuit. 

 

 

Summary of Contents for Battery Protector 100

Page 1: ...ry alarm as soon as the switch off level is reached Visual indication of the operating state Audible indication in case of preliminary alarm and disconnection can be deactivated optionally Output for external alarm indication max 0 2 A short circuit proof Input for separate sensor line for unfalsified measurement of the battery voltage Immediate emergency shut down in case of defective battery or ...

Page 2: ... controller generator charging converter etc are connected directly to the battery to ensure battery charging even with switched off battery protector Powerful inverters with own low voltage disconnection are also connected directly to the battery Option Operation with Sensor Line Sensor Selector Switch 6 Sens Set Batt to position ON Particularly in case of powerful consumer loads being equipped w...

Page 3: ...he preliminary alarm will be reset If a low voltage disconnection had been released for all that restart can be effected Automatically according to the connection voltage rates which are listed in the table charging mode or Manually at any time by means of the key EMERGENCY ON OFF or remote switch OFF and again ON Key EMERGENCY ON OFF The laterally installed key allows the following functions 1 Ma...

Page 4: ...delay times or automatic switching threshold 3 2 1 Disconnection Voltage 24 V Connection Voltage 21 2 V 40 s 24 8 V 1 s x 23 0 V 40 s 25 0 V 1 s x 23 6 V 40 s 25 6 V 1 s x x Automatic 25 0 V 2 s 3 2 1 Disconnection Voltage 12 V Connection Voltage x 10 6 V 40 s 12 4 V 1 s x x 11 5 V 40 s 12 5 V 1 s x x 11 8 V 40 s 12 8 V 1 s x x x Automatic 12 5 V 2 s The unit can extend the lifetime of Lithium LiF...

Page 5: ...rs for the correct disconnection voltage and the time If a battery is permanently discharged with only small current rates disconnection must be effected in case of higher voltage levels By this method the cells are protected from degenerative changes and lasting damages at the electrodes The disconnection will be effected at 12 2 V in 4 weeks Consumer loads with large current draw will cause a qu...

Page 6: ...rs are protected by disconnection of the supply voltage at 15 5 V 31 5 V Reconnection is effected 20 seconds after a drop below this voltage level If such high voltage levels will be reached repeatedly the charging controller the battery the charger and the battery terminals should be checked Lifetime of the battery The battery protector 100 can extend the lifetime of the battery considerably The ...

Page 7: ...of gas or dust explosion exists Observe the safety regulations Open air operation of the unit is not allowed Cables are always to be laid in such a way that damage is excluded Observe to fasten them tightly Never lay 12V 24cables and 230 V mains supply cables into the same cable conduit empty conduit Check live cables or leads periodically for insulation faults points of break or loosened connecti...

Page 8: ...ing PNP maximum 0 2 A Internal fuse 1 A self resetting after disconnection of the consumer Output Voltage During Alarm active 12 V 24 V Voltage at terminal Battery minus approx 0 3 V Output Voltage without Alarm not active 0 V Fitting Position of Unit any Working Temperature Range 20 45 C Protection Class IP21 Dimensions mm 105 x 77 x 38 mm Weight 180 g Ambient Conditions Humidity of Air max 95 RH...

Reviews: