VON MODEL SST15-832 ARC REFLECTION SECTIONALIZING SYSTEM Page 13
VI-E TESTING AN ISOLATED CABLE
NOTE: This will not work on a loop with transformers connected. The transformer will act as
a connection to ground and discharge the capacitor energy.
NOTE: This will not work on EZRS15-1264 without a voltage adjust knob.
The voltage may be adjusted using the VOLTAGE ADJUSTMENT knob. Push the START
button. If the cable is good, the voltage will not drop significantly when the gap closes and
connects the internal capacitor bank to the external cable. A small voltage drop is expected
on good cables proportional to the length of the cable due to charging current of the cable.
Push the STOP button to discharge the internal capacitor and the external cable.
VI-G RADAR OPTIONS MENU
The options menu allows you to change the default settings and access advanced features.
This menu is not normally used in day to day operation of the equipment. The available
options are different depending on the firmware revision. Please follow the onscreen
instructions for your specific firmware revision. Please contact the factory before attempting
to modify parameters in the options menu.
VII
IN CASE OF DIFFICULTY
Opening the unit should only be done by trained, and qualified individuals under consultation
with the factory.
To Open Unit remove the hex head screws from around the edge of the unit. There are ten
(10) screws total around the edge. This is most easily done with a 5/16" nut driver. Take
care to save the screws, lock washers and flat washers. The unit pulls straight up and out of
the case. About half way up you must pause, and disconnect the external 12V DC and 120-
240V AC connections. Set the unit on a clean, dry surface. If troubleshooting calls for
operation of the equipment outside the case, then the surface the unit is sitting on must be
insulating to 20kV.
IN CASE OF LOW BATTERY
In case of low or dead battery, connect the unit to 120-240V AC or and external 12V DC
source. Cables have been provided for this purpose. If the battery is low, then the unit
should begin to work immediately. If the battery has gone completely dead, then it may be
required to charge the unit for several minutes before it will come on to operate.
NOTE: The sealed lead acid battery used cannot survive discharging below approximately
10.5V. There is circuitry inside the unit that will try to prevent this situation. If this still
happens, the unit will only operate from external power and the battery needs to be replaced
as soon as possible.
More To Be Added Later