19
Group 23 EDC III
Limit values
Limit values
Limit values, electronic control unit (ECU) TAD1240GE,
TAD1241-42GE/VE
Alarm values
The maximum permissible values for charge air and coolant temperatures, for example, can be adjusted with the
parameter setting tool and can thus vary within alarm limits.
If the alarm values are exceeded, the system reduces the amount of fuel until the value is once again within the
permissible interval.
This function is a customer parameter that can be completely disengaged.
Alarm limits TAD1240–42GE/VE:
Coolant temperature:
Alarm lamp lights
Engine is switched off
Engine output 50%
Standard value Volvo Penta
98°C / 208°F
100°C / 212°F
Parameter setting (can be set
by the customer)
95–101°C / 203-214°F +2°C / 36°F over the alarm value
NOTE:
Engine protection can be switched off.
Coolant level:
Alarm lamp lights when the contact is activated and
the engine is switched off
Alarm switch is activated
NOTE:
Engine protection can be switched off.
Charge air temperature:
Standard value Volvo Penta
83°C / 181°F
85°C / 185°F
NOTE:
Engine protection can be switched off.
Oil pressure:
Standard value Volvo Penta
Idle: 0.7 bar (10,2 psi) For oil pressure 0.3 bar (4,4 psi)
lower than alarm value
>1500 RPM: 2.5 bar
For oil pressure 0.3 bar (4,4 psi)
(36,3 psi) lower than alarm value
NOTE:
Engine protection can be switched off.
Oil temperature:
Standard value Volvo Penta
125°C / 257°F
127°C / 261°F
Parameter setting (can be set
by customer)
120–130°C / 248-266°F +2°C / 36°F over alarm value
NOTE:
Engine protection can be switched off.
Fuel pressure:
Standard value Volvo Penta
<2 bar (<29 psi)
Engine not switched off
Monitor, water in fuel:
Alarm lamp lights
RPM:
Standard value Volvo Penta
Max. operational RPM + 20%
Activates upon operational RPM +15%.
Parameter setting (can be set by customer)
Max. operational RPM + 10–20%
NOTE:
Engine protection is switched off as standard.