17
6. Specifications
CAPACITY*
1000 VA / 800 W
2000 VA / 1600 W
3000 VA / 2400 W
INPUT
Voltage
Range
Low Line Transfer
160VAC/140VAC/120VAC/110VAC± 5%
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
168VAC/148VAC/128VAC/118VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
High Line Transfer
300 VAC ± 5 %
High Line Comeback
290 VAC ± 5 %
Frequency Range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power Factor
≧
0.99 @ nominal voltage (input voltage)
OUTPUT
Output voltage
200/208/220/230/240VAC
AC Voltage Regulation
± 1% (Batt. Mode)
Frequency Range
(Synchronized Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Overload
100%~110%:audible warning
110%~130%: UPS shuts down in 60 seconds at battery mode or transfer to
bypass when the utility is normal
>130%:UPS shuts down immediately at battery mode or transfer to bypass
mode when the utility is normal
Current Crest Ratio
3:1
Harmonic Distortion
≦
3 % THD (linear load)
≦
6 % THD (non-linear load)
Transfer
Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
87%
90%
Battery Mode
83%
87%
89%
BATTERY
Standard
Model
Battery Type
12 V / 9 AH 12 V / 7 AH
12 V / 7 AH
12 V / 9 AH
Numbers
2
3
6
8
6
8
Recharge Time
4 hours recover to 90% capacity (Typical)
Charging Current
1.0 A (max.)
Charging Voltage
27.3 VDC ±
1%
41.0VDC ±
1%
82.1 VDC
± 1%
109.4VDC
± 1%
82.1 VDC
± 1%
109.4VDC
± 1%
Long-run
Model
Battery Type &Numbers
Depending on the capacity of external batteries
Charging Current
1.0A/2.0A/4.0A/6.0 A ± 10%
Charging Voltage
27.3 VDC ±
1%
41.0VDC ±
1%
82.1 VDC
± 1%
109.4VDC
± 1%
82.1 VDC
± 1%
109.4VDC
± 1%
PHYSICAL
Tower
case
Dimension, D X W X H 397 X 145 X 220 (mm)
419 X 190 X 318 (mm)
Net Weight (kgs)
10
7
13
7
26
13
30.5
13
28
13 33 13
Rack
case
Dimension, D X W X H
380 x 438 x 88 (mm)
480x 438 x 88(mm)
Net Weight (kgs)
10
-
13
6.5
-
8.3
-
8.3
-
10
-
10
ENVIRONMENT
Operation Humidity
20-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 208VAC/200VAC.
** Product specifications are subject to change without further notice.