13
NOTE 2:
After turning off the UPS, please be aware that the UPS is working in Bypass mode and
there is a risk of power loss for connected devices.
2) In Bypass mode, output voltage of the UPS is still existing. In order to cut off the output, switch off
the line input breaker
(for dual input unit, also switch off the bypass line breaker). A few seconds
later, if there is no display shown on the display panel, UPS is completely off.
8. Turn off the UPS without utility power supply in Battery mode
1) Turn off the UPS by pressing “OFF” button for at least 0.5s until the buzzer will beep once.
2) The power of the output will be cut off. There is no display shown on the display panel.
9. Mute the buzzer
1) To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the
buzzer is muted, the buzzer will beep again.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the
details.
10. Operation in warning status
1) When Fault LED flashes and the buzzer beeps once every second, it means that some problems
occur during UPS operation. Users can get the warning indication from LCD panel. Please check the
trouble shooting table in chapter 4 for details.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the
details.
11. Operation in Fault mode
1) When Fault LED lights on and the buzzer beeps continuously, it means that there is a fatal error in
the UPS. Users can get the fault code from display panel. Please check the trouble shooting table in
chapter 4 for details.
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try
to turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact
the distributor or service center immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output
immediately to avoid more risk or danger.
12. Operation of changing battery numbers (only 16-pc battery model supported)
1)
This operation is only available for professional or qualified technicians.
2)
Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance
bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3)
Switch off the line input breaker (for dual input unit, also switch off the bypass input breaker), and
switch off the battery breaker (only available for long-run model).
4)
Remove the cabinet cover, and disconnect battery wire for standard model. Then modify the
jumper of JS4 & JS5 on the control board to set the battery numbers as following table.
Battery Number in series
JS5
JS4
16
0
0
18
0
1
19
1
0
20
1
1
Note: 1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.
5)
Modify the battery pack for the setting number carefully. After complete it, put the cover back,
switch on the battery breaker for long-run model.
6)
Switch on the line input breaker (for dual input unit, also switch on the bypass input breaker) and
the UPS will enter Bypass mode. If the UPS is in maintenance Bypass mode, turn the maintenance
switch to “UPS” position and then turn on the UPS.