NOTE 2:

 After turning off the UPS, please be aware that the UPS is working in Bypass mode and 

there is a risk of power loss for connected devices.   

2)    In Bypass mode, output voltage of the UPS is still existing. In order to cut off the output, switch off 

the line input breaker

 

(for dual input unit, also switch off the bypass line breaker). A few seconds 

later, if there is no display shown on the display panel, UPS is completely off. 

8. Turn off the UPS without utility power supply in Battery mode 

1)    Turn off the UPS by pressing “OFF” button for at least 0.5s until the buzzer will beep once. 
2)    The power of the output will be cut off. There is no display shown on the display panel. 

9. Mute the buzzer 

1)    To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the 

buzzer is muted, the buzzer will beep again. 

2)    Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the 

details.   

10. Operation in warning status 

1)    When Fault LED flashes and the buzzer beeps once every second, it means that some problems 

occur during UPS operation. Users can get the warning indication from LCD panel. Please check the 

trouble shooting table in chapter 4 for details.   

2)    Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the 

details. 

11. Operation in Fault mode 

1)    When Fault LED lights on and the buzzer beeps continuously, it means that there is a fatal error in 

the UPS. Users can get the fault code from display panel. Please check the trouble shooting table in 

chapter 4 for details. 

2)    Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try 

to turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact 

the distributor or service center immediately. 

3)    For  emergency  case,  please  cut  off  the  connection  from  utility,  external  battery,  and  output 

immediately to avoid more risk or danger. 

12. Operation of changing battery numbers (only 16-pc battery model supported) 

1)

 

This operation is only available for professional or qualified technicians. 

2)

 

Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance 

bypass switch on the rear panel and turn the maintenance switch to “BPS” position first. 

3)

 

Switch off the line input breaker (for dual input unit, also switch off the bypass input breaker), and 

switch off the battery breaker (only available for long-run model).   

4)

 

Remove  the  cabinet  cover,  and  disconnect  battery  wire  for  standard  model.  Then  modify  the 

jumper of JS4 & JS5 on the control board to set the battery numbers as following table.   

Battery Number in series 

JS5 

JS4 

16 

18 

19 

20 

Note: 1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.

 

5)

 

Modify the battery pack for the setting number carefully. After complete it, put the cover back, 

switch on the battery breaker for long-run model. 

6)

 

Switch on the line input breaker (for dual input unit, also switch on the bypass input breaker) and 

the UPS will enter Bypass mode. If the UPS is in maintenance Bypass mode, turn the maintenance 

switch to “UPS” position and then turn on the UPS. 

Summary of Contents for Galleon II 3P

Page 1: ...3 3 30K 40K Online UPS Uninterruptible Power Supply System Version 1 0 User Manual...

Page 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Page 3: ...LATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 SINGLE UPS OPERATION 11 3 5 PARALLEL OPERATIO...

Page 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Page 5: ...ipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence...

Page 6: ...mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Condu...

Page 7: ...tion Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only av...

Page 8: ...nel Diagram 5 30KL 40KL Diagram 6 30K 40K Input output Input Output Terminal Terminal 1 RS 232 communication port 2 USB communication port 3 Emergency power off function connector EPO connector 4 Shar...

Page 9: ...burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table Mo...

Page 10: ...stalled If not please install it carefully Switch off the battery breaker before installation NOTE Set the battery pack breaker in OFF position and then install the battery pack Pay highly attention t...

Page 11: ...utput wires of each UPS to an output breaker 3 Connect all output breakers to a major output breaker which will be directly connected to the loads 4 Each UPS is connected to an independent battery pac...

Page 12: ...ay next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s until the buzzer is mute Please refer to section 3 4 9 for details Down key Press this button...

Page 13: ...voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Page 14: ...PS operates in Bypass mode and supplies power to the loads via the bypass NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on the input breaker In B...

Page 15: ...12 for detailed setting is consistent to real connection 5 Battery mode operation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity...

Page 16: ...ult code from display panel Please check the trouble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery and so on after the fault occurs Don t try to t...

Page 17: ...zero that means all connections are correct Otherwise please check if the wirings are connected correctly b Turn on the output breaker of each UPS c Turn on each UPS in turns After a while the UPSs wi...

Page 18: ...Bypass mode Set the maintenance switches from BPS to UPS and put the maintenance bypass covers back 5 Turn on the remaining UPS according to the previous section Warning Only for the parallel system...

Page 19: ...for future options 11 Hot Standby Function Setting Y 12 Neutral loss detection Y Y Y Y Y Y 13 Battery voltage calibration Y Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y Y 15 Inverter A voltage ad...

Page 20: ...ter 3 Frequency mode Setting output frequency at CVCF mode or not CVCF mode You may choose the following two options in parameter 3 CF Setting UPS to CVCF mode If selected the output frequency will be...

Page 21: ...nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface Setting Parameter 2 Set low voltage point...

Page 22: ...etection function The UPS will not detect the neutral loss or not ATO The UPS will automatically detect the neutral is lost or not If neutral loss is detected an alarm will be generated If the UPS is...

Page 23: ...suitable to battery specifications 15 Inverter A voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter A voltage Parameter 3 the voltage range is from 0V to 9...

Page 24: ...verter B 20 Output C voltage calibration Interface Setting Parameter 2 it always shows OP V as output voltage Parameter 3 it shows the internal measurement value of the output C voltage and you can ca...

Page 25: ...oltage frequency is out of acceptable range or bypass is disabled or forbidden UPS will enter no output mode if powering on or turning off the UPS It means the UPS has no output Alarm beeps every two...

Page 26: ...23 ECO mode Description When the input voltage is within voltage regulation range and ECO mode is enabled UPS will bypass voltage to output for energy saving LCD display...

Page 27: ...ency 50 Hz or 60 Hz In this mode the UPS will have no bypass output but still charge the battery LCD display Battery mode Description When the input voltage frequency is beyond the acceptable range or...

Page 28: ...pass mode Alarm beeps every two minutes LCD display Battery Test Description When UPS is in AC mode or CVCF mode press Test key for more than 0 5s Then the UPS will beep once and start Battery Test Th...

Page 29: ...will be flashing and it can show up to 3 error codes and each code indicates one error You can refer to the meaning of the icon in the warning code table LCD display Fault status Description When a f...

Page 30: ...ases are incompatible None 17 Inverter A B output line to line short circuited 50 Inverter STS Short circuited None 18 Inverter B C output line to line short circuited 51 Battery wiring fault None 19...

Page 31: ...l system 04 IP phase abnormal 33 Locked in bypass after overload 3 times in 30 minutes 05 Bypass phase abnormal 34 Converter current unbalance 07 Over charge 3A Cover of maintain switch is open 08 Low...

Page 32: ...tinue the UPS will be locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 4...

Page 33: ...nection If the connection is ok and the alarm is still displaying please refer to the LCD setting section to access the neutral loss program If CHE is shown in the parameter 3 please press the Enter k...

Page 34: ...ries and with the required precautionary measures can replace the batteries and supervise the operations Unauthorized staff must be kept away from the batteries Verify that no voltage exists between t...

Page 35: ...CY AC mode 94 94 Battery Mode 92 92 BATTERY Type 12 V 7 Ah Depending on applications 12 V 9 Ah Depending on applications Numbers 16pcs 2strings 16 20 16pcs 2strings 16 20 Recharge Time 9 hours recover...

Reviews: