WIRING
This product should only be installed by a licenced electrician in accordance with all the
requirements of AS/NZS 3000 (current edition) and other relevant Standards and Regulations
IP RATINGS
PLACEMENT
To maintain IP66 rating, all used cable entries must be sealed with a silicone sealant and front cover screws
must be fully tightened, with all screw blanking plugs used cable entries.
The Sunset Switch should be placed where it receives sufficient indirect sunlight, preferably facing south.
When power is first applied, the unit will switch ON for a one-minute test period and will then resume normal
operation.
The unit should not be installed where,
Basic Installation
Installation with override ON
1.
the translucent front cover receives direct sun light, or,
2.
where the Sunset Switch receives light directly from the lights it is switching, otherwise the load may
switch ON and OFF at 1-minute intervals.
INSTALLATION
TESTING
To test the Sunset Switch during daylight hours, after the initial one-minute test period, fully cover the unit with
the product box (with black insert) and wait for at least one minute until the load turns ON.
MODES OF OPERATION
Delay OFF timer Examples
MODE1 -
DUSK-DAWN MODE (
DEFAULT
) (ALL SWITCHES OFF)
MODE2 -
DELAY TIMER MODE (SWITCHES 6,7 & 8 OFF)
A fixed delay time of 30 minutes up to 15 hours and 30 minutes can be set.
Switches 6-8 are in the OFF position. Switches 1-5 as set to provide the required delay OFF time.
Switches 1-5 used to set ON
time after dusk
Switches 6,7,8
alsways OFF in Delay
Timer Mode
ON at dusk, OFF at Dawn
Fixed-ON time after dusk
Electrical safety warning
Isolate the device from the mains power supply before setting the required mode of operation
1 hours after dusk
5 hours after dusk
2 hours after dusk
6 hours after dusk
3 hours after dusk
7 hours after dusk
4 hours after dusk
ON time after dusk
ON time after dusk
Switch positions