UL CONDITIONS OF ACCEPTABILITY

The following are among the considerations to be made in judging the acceptability of the table assembly:

1.  The Downdraft Table is to be used in conjunction with up to three Listed commercial cooking appliances.  

See “COOKING APPLIANCE CONSTRAINTS” Ills. 1-6 for specific cooking appliances that can be used and 

on which shelf height. Total electrical load does not exceed 50 A for all appliances combined (based on 

contactor employed). Downdraft units are marked with these details including shelf height.   

2.  The acceptability of the installation of the downdraft table assembly shall be determined under end-product 

application.  The downdraft assembly shall be adequately enclosed to render inaccessible all or any parts 

of the equipment that involve a risk of electric shock or injury to persons, and preclude propagation of 

flame initiated by electrical disturbances occurring within.  The assembly shall meet relevant end-product 

requirements, including the enclosure, accessibility of uninsulated live and/or moving parts that may involve 

a risk of electric shock and fire, and/or injury to persons, respectively, spacings and segregation, grounding, 

polarization, and marking requirements under the end-product application.  

3.  In addition, the acceptability of the use of the downdraft table assembly shall be made in conjunction with 

the end-product requirements specified in the Standard for Commercial Electric Cooking Appliances, UL 

197, for UL Listing (UL).  

4.  The acceptability of the supporting/mounting means and securement of the downdraft table assembly shall 

be determined under the end-product application.

5.  The downdraft assembly terminations and wiring shall be suitable, protected from damage and sharp edges, 

etc., and enclosed.  In addition, any flexing or movement of the leads/wiring during normal operation or any 

user servicing shall be investigated and determined to be acceptable.   

6.  The downdraft table assembly shall be provided with suitable grounding/bonding means under the end-

product application.

7.  The following tests have been conducted in accordance with UL 710B on the covered downdraft table 

with griddle assembly:  Power Input (Rating), Normal Temperature (Normal), Dielectric Voltage-Withstand 

(Dielectric Strength), Insulation Resistance, Grounding and Bonding, Stability, Strain Relief, Push-Back Relief.  

Consideration shall be given to re-conducting any of the tests above with other end-product appliances.

8.  In addition to the above, the following tests have been conducted in accordance with UL 710B on the cov-

ered downdraft table with griddle assembly and fryer and hot plate: Lower Airflow Determination, Capture, 

Emissions (EPA 202), Fire Extinguishment (General), and Fire Extinguishment (Griddles). Consideration shall 

be given to re-conducting any of the tests above with end-product griddle paying attention to Griddle Watt, 

Griddle size, Griddle max temperature, and maximum food load and throughput. 

9.  The end-product report shall include a detailed description of the  downdraft table including specific mark-

ings for applicable cooking appliances that may be used.  Also includes the details for the cooking appliance 

shelf height for each appliance.

10. The covered Downdraft table assembly component is intended to be factory installed only.
11. If legs/feet or casters are not provided as part of the Recognized Component table, the supporting means 

should be evaluated in the end use and Stability Test should be considered.

Summary of Contents for FlexVent

Page 1: ...2022 The Vollrath Company L L C 7 15 2022 FlexVent Versatile Slide In with Downdraft Vent System and Fire Suppression INSTALLATION MANUAL...

Page 2: ...onnect unit from electrical supply before any servicing could result in death serious injury or equipment damage Unit must be installed by qualified personnel in accordance with applicable codes and o...

Page 3: ...closure provides adequate ventilation as specified in this manual NOTE UNPACKING INSTALLATION Ensure there is enough space to unpack there will be layers of protective packaging Use care when unpackin...

Page 4: ...rview 8 Required Parts Supplied by Installer 9 UL Conditions of Acceptability 10 System Overview 11 Cabinet Constraints Installation 12 LED Lighting Optional 13 Cooking Appliance Constraints Electric...

Page 5: ...Flexvent installation manual 5 BACK TO TOC...

Page 6: ...nd operation of FlexVent This unit has been designed for customized over under or flush counter instal lation in the front or back of the house as determined by the Authority Having Jurisdiction AHJ T...

Page 7: ...easured when utilizing this unit FlexVent has been evaluated for zero clearance surround installation Ceiling height must be at least 96 DESCRIPTION MAIN SYSTEMS FlexVent Downdraft Recirculating Venti...

Page 8: ...ing option Cuts Cooking Station outlet power if there is a pressure error or fire C Recirculating Filtration Ductless Hood Assembly Hood plenum and ductwork stainless steel Baffle type grease filters...

Page 9: ...sant Supplied by ANSUL Representative Electrical Circuit breaker box Circuit breakers Appliance outlets Appliance conduit and wiring etc for customized configuration Mechanical Cabinet surround counte...

Page 10: ...he end product application 5 The downdraft assembly terminations and wiring shall be suitable protected from damage and sharp edges etc and enclosed In addition any flexing or movement of the leads wi...

Page 11: ...Filters 2 C Grease Tray 1 D Manual Pull Station E Fire Suppression System Arming View Window F 1 5 Gallon Ansulex R 102 Tank Ansulex Fire Suppressant G Electrical Outlets H Pressure Control I Interlo...

Page 12: ...2 1 2 133 4 53 5 8 136 2 28 7 8 73 2 TOP OF COUNTERTOP COUNTERTOP BASE DIMENSIONS RESULT IN APPLIANCE 7 8 2 2 CM ABOVE COUNTERTOP APPLIANCE OVERLAPS COUNTERTOP APPROXIMATELY 1 2 1 3 CM ON ALL SIDES 34...

Page 13: ...lay Press again to disable OFF will display on light system on high pressure dirty or wrong filter low pressure missing or wrong filter main power 3 Press Main Power switch to exit LED setup mode NOTE...

Page 14: ...fall within the Effluent Capture and Fire Suppression Boundaries 7 200 W maximum 30 amps 120 or 240 V AHJ approvals are required for all appliances and configurations Usable appliance space 18 1 4 D...

Page 15: ...Flexvent installation manual 15 BACK TO TOC...

Page 16: ...ONSTRAINTS ELECTRIC ONLY Induction HOB s Hot Plate s Shelf Position Max Temp Max Watts Pot Pan Dia Max 1 3 Any 550 F 3600 hob 7200 total 14 Shelf positions are top middle and bottom COOKING SURFACE HE...

Page 17: ...OT PLATE CONSTRAINTS ELECTRIC ONLY Continued Induction HOB s Hot Plate s Shelf Position Max Temp Max Watts Pot Pan Dia Max 1 3 Any 550 F 3600 hob 7200 total 14 Shelf positions are top middle and botto...

Page 18: ...ELECTRIC ONLY 66 mg m3 per 15 lb vat Fryer s Max Capacity Shelf Position Max Temp Max Watts Max Surface Oil 1 3 15 lbs oil vat Bottom 375 F 3600 vat 7200 total 132 sq in vat COOKING SURFACE HEIGHT LI...

Page 19: ...ONSTRAINTS ELECTRIC ONLY 2 95 mg m3 per 396 sq in cooking surface s Griddle s Shelf Position Max Temp Max Watts Max Surface Area 1 2 Bottom 550 F 3600 total 396 sq in COOKING SURFACE HEIGHT LIMIT COOK...

Page 20: ...ts Max Pan Diameter 1 2 Bottom 550 F 3600 hob 7200 total 14 COOKING SURFACE HEIGHT LIMIT SANDWICH PANINI GRILL CONSTRAINTS ELECTRIC ONLY Sandwich Panini Press es Shelf Position Max Temp Max Watts 1 3...

Page 21: ...Flexvent installation manual 21 BACK TO TOC APPLIANCE NOZZLE LOCATIONS AND SETUP SHELF TO BE IN LOWEST POSITION 9 1 8 23 2 12 30 3 12 30 3...

Page 22: ...ain this unit properly can result in property damage injury or death The following information is for use by authorized ANSUL representatives only Refer to ANSUL documentation for the following steps...

Page 23: ...rder NOTE Ensure the Particulate Filters are properly oriented per the label A Grease Filters 2 352035 2 B Drip Tray 352034 2 C Particulate Filters 2 352010 1 A B C System Cleaning and Maintenance Pro...

Page 24: ...NPUT GROUND INPUT NEUTRAL MAIN POWER SIGNAL INPUT L1 HIGH PRESSURE PIN 1 PIN 2 PIN 3 PIN 4 PIN 5 PIN 7 PIN 8 PIN 9 SIGNAL OUTPUT L1 LIGHT PIN 6 R3 R4 R5 USER INTERFACE 18 19 1 2 WHITE M1 10VDC RED SPE...

Page 25: ...RFACE R5 R4 R3 PIN 6 SIGNAL OUTPUT L1 LIGHT PIN 9 PIN 8 PIN 7 PIN 5 PIN 4 PIN 3 PIN 2 PIN 1 SIGNAL INPUT L1 HIGH PRESSURE MAIN POWER INPUT NEUTRAL INPUT GROUND SIGNAL OUTPUT L1 SYSTEM START SIGNAL INP...

Page 26: ...R2 POWER RELAY ENERGIZED WHEN R4 IS CLOSED R3 FAN START RELAY ENERGIZED CLOSED WHEN START IS PRESSED WILL DE ENERGIZE ON SUBSEQUENT PRESS OF START DELAY OPEN ON LOW PRESSURE FAULT 220 SECONDS NO OPEN...

Page 27: ...Flexvent installation manual 27 BACK TO TOC...

Page 28: ...set circuit breaker for unit Contact Vollrath Technical Services Contact an authorized ANSUL representative for repair Low Pressure Indicator is illuminated and cooking unit will not turn on Particula...

Page 29: ...y does not apply to products purchased for personal family or household use and The Vollrath Company LLC does not offer a written warranty to purchasers for such uses The Vollrath company LLC warrants...

Reviews: