Quick Installation Guide

Wireless Wall Controller

1. WIRE FAN AND MODULE

READ AND SAVE THESE INSTRUCTIONS

WARNING: Disconnect power to the installation locations before installing the fan and controller.
WARNING: Installation work and electrical wiring must be done by qualified person(s) in accordance with all 
applicable codes and standards, including fire-rated construction. Incorrect assembly can cause electric shock 
or damage the motor and the controller.
CAUTION: The Big Ass Fans product warranty will not cover equipment damage or failure that is caused by 
improper installation or use.
CAUTION: Do not mount the wireless wall controller outdoors or in a location where it may come into contact 
with water.

120–240 VAC Mains Input

L1

L2/N

GND

North America 
100–120 V

Black

White

Green 

or Bare 

Copper

North America 
208–240 V

Black, Red, 

or Blue

Red, Blue, 

or Black

Australia

Brown or 

Red

Black or 

Light Blue

Green 

with 

Yellow 

Tracer

All Other 
Regions

Brown

Blue

Fan Power Cable

L1: Black or Brown

L2/N: White or Blue

GND: Green or Green/Yellow

Fan Controller Input Cable

See table below.

Fan Controller Input Cable

1 White

+0–10 VDC Speed Ref.

2 Brown

Not Used

3 Orange Status LED (+)
4 Yellow

Run Enable

Closed: Enable

5 Blue

Open: Disable

6 Green

Status LED (-)

7 Red

+10 VDC Supply

8 Black

DC Common

If a wall controller is already installed with the fan, uninstall it before beginning wireless wall controller installation.

Black: L1

White: L2/N

Green: GND

Red: LOAD (Not used, cap off)

120–240 VAC Mains Input

See table below.

Black and Pink: 0 VDC

White and Violet: 0–10 VDC Ref.

Fan Blue and Yellow: Run Enable

Consult fire alarm interface instructions if 

applicable.

Brown, Orange, Green, Red: 

Not used, cap individually

Online Wiring 
Diagram