6.12 Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom
of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge
the air (be careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
4. Disconnect the charge hose from the 3-way valve
’
s service port immediately.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the
air conditioner before disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap.
Be sure to check for gas leakage.
文件使用
"pdfFactory Pro"
试用版本创建
www.fineprint.cn
Summary of Contents for ACP-09CH25AEI
Page 2: ......
Page 12: ...9 3 Dimension 3 1 Indoor Units For ACP 09CH25AEI ACP 12CH35AEI ACP 12CH35AECI models ...
Page 15: ...12 4 Refrigerant Cycle Diagram PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Page 17: ...14 ACP 18CH50AEI ACP 24CH70AEI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Page 18: ...15 ACP 09CH25AEI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Page 19: ...16 ACP 18CH50AEI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Page 20: ...17 ACP 09CH25AEI ACP 12CH35AEI ACP 12CH35AECI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Page 21: ...18 ACP 24CH70AEI PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...
Page 52: ......
Page 53: ......
Page 54: ......