Artful Series

Timer function

Displayer

TURBO function

Up\Down swing fan function

Basic display

The common setting for Timer:

a.Timer on: At unit off, can set up the Timer On function,when Timer On act, the controller will run at original setting mode, the Timer
interval is 0.5hr, setting range is 0.5-24hrs. 
b.Timer off: At unit on, can set up the Timer Off function, when Timer Off act, the unit will turn off, the Timer interval is 0.5hr, setting range
is 0.5-24hrs.

Hours setting for Timer:

a. Timer on: If unit is running then to set up the Timer On, the unit will go on running, if the unit is off to set up the Timer On, when Timer On
act, the unit will run at the presetting modes.

b. Timer off: If unit is off then to set up the Timer Off, when setting the Timer off, the unit stand by, if unit is turned on to set up Timer Off,
when the Timer Off act, the system will stop to work.

c. Timer change: When unit is running in Timer mode, by operate the On/Off of remote controller to turn on or turn off the unit, can reset up
the Timer function, the unit will run at the mode of last setting. 

If unit is running, at the same time to set up Timer On and Timer Off, the system will keep the present setting status, after the Timer Off   

When system is running, at the same time to set up Timer On and Timer Off, the unit will keep the current presetting working status, if
Timer Off act, the unit will stop working. 

When unit is stop running, at the same time to set up the Timer On and Timer Off, the unit will keep stop running, until Timer On act, the
unit will start to work, after this when Timer On of every day act, it will run at presetting modes, when Timer Off act, the unit will stop to work.  

If the setting for the Timer Off and Timer On are the same, the Timer Off will act.

Memory function

Contents of memory: Modes, Up and Down Swing, Light, Setting Temp. Setting fan speed, Common setting for Timer (Hours will not 
memorized). After Timer Off, when repower on, the unit will automatically turn on and run at memorized contents.  
There is no Timer Setting in the remote control order that the unit will memorize the remote control order of last setting and it will run
at that mode.  

There is common setting for Timer of last setting by remote controller, before the Timer act, if power off and after powered on, the unit will 
memorize the timer of last setting by remote control, the timer will recalculate after powered on.  
There is Timer function at last setting by remote control, if Timer function has act, the power off after Timer On or Timer Off, after powered
on, the unit will memorize the running mode before power off, under Hours setting for Timer, the memory is invalid. 

I Feel function

When controller received the orders that the controller will work according to ambient temperature which is sent by remote control (Except
Defrost and Anti-cool wind, it will still adopt the air conditioner self ambient sensor sampling value), the remote control in every 10mins, to
sent the ambient temperature value to controller. 11mins later, the controller haven’t received the ambient temperature value from the
remote control that the air conditioner will run itself ambient temperature. If there is no setting function that the ambient temperature will
adopt the AC sensor sampling value. Power off will not memorize this function.     

Only in Cool or Heat mode, the Turbo setting is available, when controller received this order, the indoor fan will run at super high,
sent the outdoor unit Turbo signal and sent the high fan speed.  

After powered on, the up and down swing motor will firstly rotate the air guide board to postion O in anticlockwise, turn off the air vent. After
unit is turned on, if there is no swing function set up, under the Heat mode or Auto Heat mode, the up and down air guide board will rotate to
position D in clockwise; In other modes, the up and down guide board will roate to horizontal position L1 clockwise. When turning on the unit
to set up swing function synchronously. If unit is turned on to set up the swing function that the guide louver will swing between L and D.
There are 7 kinds of status of swing for guide louver: Position L, Position A, Position B, Position C, Position D, Position L and Position D,
Position L to Position D to stop swing ( the inclination between L-D is conformal). When unit is off the air guide louver will close and turn
to position 0. The swing is only valid while setting swing order and indoor fan motor is running.

Heating angle

Cooling angle

Angle

Angle

When unit is running in cooling and dehumidifying mode, after sleep set up 1hr later, Tset will be increased 1    ; 2hrs later, Tset will be
increased 2    , the Tset will not be exceeded 30      ; In heating mode, after sleep procedure set up 1hr later, Tset declined 1    ,  2hrs 
later,  Tset will be declined 2    ;  the Tset will not be exceed 16      , under Fan and Auto modes, the setting temperature will not be changed.    

Summary of Contents for ACP-07CIFM21GEI

Page 1: ...ACP 07CIFM21GEI ACP 09CIFM25GEI ACP 12CIFM35GEI ACP 18CIFM50GEI RoHS Service manual ENG ...

Page 2: ......

Page 3: ...tor uF 1 1 1 1 Fan Motor RLA A 0 23 0 23 0 23 0 19 Fan Type Piece Cross flow fan 1 Cross flow fan 1 Cross flow fan 1 Cross flow fan 1 Diameter Length mm Ø85 X 615 Ø85X615 Ø85X668 Ø98 X 733 Evaporator Aluminum fin copper tube Aluminum fin copper tube Aluminum fin copper tube Aluminum fin copper tube Pipe Diameter mm Ø7 Ø7 Ø7 Ø7 Row Fin Gap mm 2 1 6 2 1 6 2 1 5 2 1 5 Coil length l x height H x coil ...

Page 4: ...me Indoor unit Front panel Air intake LCD display Filter Guide louver board Air outlet Wireless remote control Displayer Cool Dry Heat Power Run Window receiver Setting temp Wrapping Tape Wall pipe Artful Series ...

Page 5: ...4 Outline and dimension Left tube exit Right tube exit Unit mm Dimension Applicable models Ceiling Wall Mounting Plate Outline and installation dimension ...

Page 6: ...RIC BOX I I II I EVAPORATOR EARTHING PANEL AC L BK INDOOR UNIT BK PIPE OUT DISP1 AP1 DISPLAY ROOM TUBE TR OUT M2 SWING UD TRANSFORMER I TR IN TC ROOM RT3 0 AP2 BN PG RT4 0 M1 BU FAN OUTDOOR UNIT BN 2 YEGN 3 BU XT N 1 PIPE MID 0 RT2 0 RT1 PIPE IN SWING MOTOR2 COMU PTC TUBE I TUBE O DISP2 N1 PGF MOTOR YEGN 3 2 4 CAP JUMP E YEGN E E TEM SENSOR TEM SENSOR TEM SENSOR TEM SENSOR ACP 18CIFM50GEI ...

Page 7: ...he compressor stops running including any sensor malfunction indoor unit blows surplus heat 3 Anti cool wind indoor fan will run after 2mins delayed Blowing surplus heat Indoor fan will stop running after 60s and running at the speed before it stop the fan speed can not be changed Blowing surplus heat the guide board opened at minimum angle 4 When defrosting oil return indoor unit will stop do not...

Page 8: ...g by remote control the timer will recalculate after powered on There is Timer function at last setting by remote control if Timer function has act the power off after Timer On or Timer Off after powered on the unit will memorize the running mode before power off under Hours setting for Timer the memory is invalid I Feel function When controller received the orders that the controller will work ac...

Page 9: ...nction need to use remote control for transfer within 3s continuously press SLEEP button for 6 times will display 5min will automatically quit detection status invalid in Auto mode or within 3s continuously press SLEEP button for 6 times will quit Note if several malfunction exist synchronously the malfunction code will display circularly Indicator will blink 0 5s and extinguish 0 5s Defrosting oi...

Page 10: ... the joint to lift up the panel to make the front panel get clear of the clasps can take down the front panel Front panel LCD Cover board Bolts Disassemble Filter and top cover Push the filter inward and then pull it upward to remove it Unscrew the screw fixing the top cover of electric box to remove the top cover Filter Clasps Cover of electric box Disassemble Guide Louver Manually bend the guide...

Page 11: ...ew Electric box cover Disassemble electric box Firstly screw off 2pcs screw from electric box Then pull out the wire terminal of motor screw off 3pcs earth screw lift it up can take down the elec tric box Firstly to screw off earth screw of electric box cover loosen clasp disassemble the electric box cover then take off the wire terminal of air guide motor to screw off 2pcs screw from water tray t...

Page 12: ...assemble Evaporator Rear pipe clamp Screw Screw Remove the left two screws at the evaporator Remove the left two screws at the evaporator turn the evaporator with certain angle then move the ecaporator Screw Artful Series Operating Procedures Photos 11 ...

Page 13: ...edures Photos Unscrew the three screws fixing the motor clamp loosen the screws holding on the motoe and cross flow fan then you can remove motor and cross flow fan Disassemble Motor and cross flow fan Screw Screw 12 ...

Page 14: ...8 Artful Series Explosive view for indoor unit Explosive view and parts list for indoor unit ...

Page 15: ...04 20192104 1 19 Front Panel 200027185 200027185 1 20 Transparent Mirror 22432262 22432262 1 21 Receiver Board D5003C 30565002 30565002 1 22 Display Box 20122041 20122041 1 23 Display Box Cover 20122042 20122042 1 24 Remote Control YT1F 30510049 30510049 1 25 Covering Plate 2 20122075 20122075 1 26 Motor MP28VB 15012086 15012086 1 27 Motor Clamp 26112116 26112116 1 28 Motor FN10A PG 15012078 15012...

Page 16: ...Artful Series Explosive view of parts for indoor unit ...

Page 17: ...l C 0 2 3 1 0 0 0 4 8 0 7 t e n g a M 1 2 1 2 6 2 2 3 4 2 2 r o r r i M t n e r a p s n a r T 2 2 1 2 0 0 5 6 5 0 3 C 3 0 0 5 D d r a o B r e v i e c e R 3 2 1 1 4 0 2 2 1 0 2 x o B y a l p s i D 4 2 1 2 4 0 2 2 1 0 2 r e v o C x o B y a l p s i D 5 2 1 9 4 0 0 1 5 0 3 F 1 T Y l o r t n o C e t o m e R 6 2 1 4 7 0 2 2 1 0 2 e t a l P g n i r e v o C 7 2 1 6 8 0 2 1 0 5 1 B V 8 2 P M r o t o M 8 2 ...

Page 18: ...Artful Series Explosive view of parts for indoor unit ...

Page 19: ...iece 22432269 1 20 Receiver Board D5003C 30565002 1 21 Clamp 20122041 1 22 Clamp 20122042 1 23 Remote Control YT1F 30510049 1 24 Covering Plate 20114009P 1 25 Motor MP28VB 15012086 1 26 Motor Clamp 26114094 1 27 Motor FN20C PG 15012077 1 28 Terminal Board 42011233 1 29 Electric Box Cover 20114008 1 30 Electric Box 20114007 1 31 Main PCB M514F2HJ 30035286 1 32 Jumping Connector 4202300107 1 33 Tran...

Page 20: ......

Page 21: ......

Page 22: ......

Reviews: