6.4.3.3 Defrosting mode 

If any one of the following items is satisfied, AC 

will enter the defrosting mode. 

After  the  compressor  starts  up  and  keeps 

running, mark the minimum value of T3 from the 

10th minutes to 15th minutes as T30. 

1)If the compressor cumulate running time is up 

to  29  minutes  and  T3<  TCDI1,  T3

T30SUBT3ONE

T30. 

2)If the compressor cumulate running time is up 

to  35  minutes  and  T3<  TCDI2,  T3

T30SUBT3TWO

T30. 

3)If the compressor cumulate running time is up 

to 40 minutes and T3< TCDI3 for 3 minutes. 

4)If the compressor cumulate running time is up 

to 120 minutes and T3<-15

Condition of ending defrosting: 

If any one of the following items is satisfied, the 

defrosting will finish and the machine will turn to 

normal heating mode. 

----T3 rises to be higher than TCDE1

----T3 keeps to be higher than TCDE2

  for 80 

seconds. 

----The  machine  has  run  for  10  minutes  in 

defrosting mode. 

Defrosting action

 

 

4-Way valve 

Indoor fan 

Outdoor fan 

480P

 

PMV 

PMV running   

4 mins with 480P 

Compressor 

10S

 

30S

 

TimeA 

10S 

no longer than 10min 

Cool-F9 

Anti cold wind

 

 

6.4.4 Auto-mode 

This mode can be chosen with remote 

controller and the setting temperature can be 

changed between 17

°C~30°C 

In auto mode, the machine will choose cooling, 

heating or fan-

only mode according to ΔT (ΔT 

=T1-Ts). 

ΔT=T1-Ts 

Running mode 

ΔT

2

 

Cooling 

-

2≤ΔT≤2

 

Fan-only 

ΔT<-2

 

Heating 

Indoor  fan  will  run  at  auto  fan  of  the  relevant 

mode. 

The louver operates same as in relevant mode. 

If the machine switches mode between heating 

and cooling, the compressor will keep stopping 

for 15 minutes and then choose mode 

according to T1-Ts. 

If the setting temperature is modified, the 

machine will choose running function again. 

 

6.4.5 Drying mode 

Indoor fan speed is fixed at breeze and can’t be 
changed.  The  louver  angle  is  the  same  as  in 

cooling mode. 

All protections are active and the same as that in 

cooling mode. 

 

6.4.6 Forced operation function 

6.4.6.1 Enter forced operation function: 

Press  the  touch  button  continually,  the  AC  will 

run as below sequence: 

Summary of Contents for ACP-07CIFM21AERI

Page 1: ...VIVAX WALL TYPE MULTI TYPE Service Manual 2016 ACP 07CIFM21AERI ACP 09CIFM25AERI ACP 12CIFM35AERI ACP 18CIFM50AERI ...

Page 2: ...y Precaution 3 1 2 Warning 3 2 Function 6 3 Dimension 7 4 Wiring Diagram 8 5 Operation Characteristics 10 6 Electronic function 11 6 1 Abbreviation 11 6 2 Display function 11 6 3 Main Protection 12 6 4 Operation Modes and Functions 12 ...

Page 3: ...areful of the case edges and the fins on the condenser and evaporator For installation always contact the dealer or an authorized service center Do not install the product on a defective installation stand Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall with it causing property damage product failure and personal injury Do not let th...

Page 4: ...e that water is drained away properly A bad connection may cause water leakage Keep level even when installing the product It can avoid vibration of water leakage Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods It may cause a problem for your neighbors Use two or more people to lift and transport the product Do not install the product wher...

Page 5: ...e control with new ones of the same type Do not mix old and new batteries or different types of batteries There is risk of fire or explosion Do not recharge or disassemble the batteries Do not dispose of batteries in a fire They may burn of explode If the liquid from the batteries gets onto your skin or clothes wash it well with clean water Do not use the remote of the batteries have leaked ...

Page 6: ...I 18K ACP 18CIFM50AERI 24K Cold catalyst filter Silver Ico Filter O Vitamin C Filter O 3M HAM Filter O Bio Filter O Golden Fin O Ionizer O Compressor Crankcase Heater O 1W Standby O Louver Position Memory Function Self diag Function Hydrophilic Aluminum Fin Anti rust Cabinet Valve Protection Cover PTC Heating Belt O Filter 2 ways of drainage O optional ...

Page 7: ...3 Dimension For ACP 07CIFM21AERI ACP 09CIFM25AERI For ACP 12CIFM35AERI Model W D H ACP 07CIFM21AERI 722 187 290 ACP 09CIFM25AERI 722 187 290 ACP 12CIFM35AERI 802 189 297 ACP 18CIFM50AERI 965 215 319 ...

Page 8: ...For ACP 18CIFM50AERI 4 Wiring Diagram ACP 07CIFM21AERI ACP 09CIFM25AERI ACP 12CIFM35AERI ACP 18CIFM50AERI ...

Page 9: ......

Page 10: ...ION 1 If the air conditioner is used beyond the above conditions certain safety protection features may come into operation and cause the unit to operate abnormally 2 The room relative humidity should be less than 80 If the air conditioner operates beyond this figure the surface of the air conditioner may attract condensation Please set the vertical air flow louver to its maximum angle vertically ...

Page 11: ...ture settings when the air conditioner is operational Displays the room temperature in FAN mode Displays the self diagnostic codes Dispalys for three seconds when Timer ON Fresh Swing Turbo or Silence feature is activated Dispalys for three seconds when Fresh Swing Turbo or Silence feature is cancelled Dispalys under deforsting operation Dispalys when anti cold air feature is activated under heati...

Page 12: ...lled by anti cold wind function 6 3 5 Sensor protection at open circuit and breaking disconnection 6 4 Operation Modes and Functions 6 4 1 Fan mode 1 Outdoor fan and compressor stop 2 Temperature setting function is disabled and no setting temperature is displayed 3 Indoor fan can be set to high med low auto 4 The louver operates same as in cooling mode 5 Auto fan a b c d 5 0 4 0 2 5 1 0 6 0 T1 24...

Page 13: ...g rules The compressor will run at corresponding frequency according to the gross amendatory capacity demand Frequen cy 0 HEAT _F1 HE AT HEAT_ F15 HE AT _F2 _F1 6 Amenda tory capacity demand 0 1 2 15 16 6 4 3 2 Outdoor fan running rules 21 19 A C 18 16 D 15 13 12 10 B E Heating 6 4 3 3 Indoor fan running rules When the compressor is on the indoor fan can be set to high med low auto And the anti co...

Page 14: ...0 minutes in defrosting mode Defrosting action 4 Way valve Indoor fan Outdoor fan 480P PMV PMV running 4 mins with 480P Compressor 10S 30S TimeA 10S no longer than 10min Cool F9 Anti cold wind 6 4 4 Auto mode This mode can be chosen with remote controller and the setting temperature can be changed between 17 C 30 C In auto mode the machine will choose cooling heating or fan only mode according to ...

Page 15: ... when reaching the setting off time and then turn on automatically when reaching the setting on time 6 4 7 6 The timer function will not change the AC current operation mode Suppose AC is off now it will not start up firstly after setting the timer off function And when reaching the setting time the timer LED will be off and the AC running mode has not been changed 6 4 7 7 The setting time is rela...

Page 16: ...ection function of room temperature sensor will be shielded but the error detective function of room temperature sensor will be still valid 2 When the follow me function is available the PCB will control the unit according to the room temperature from the remote controller and the setting temperature 3 The PCB will take action to the mode change information from remote controller signal but it wil...

Reviews: