Vista VID-W20L030 Installation Manual Download Page 3

 
 
 
 

Manual VID-W20L030_1 2008.doc / page 3 (10) 

 

www.norbain.co.uk

 

1 Introduction 

The VID-W20L030 is a highly sensitive Passive Infrared Detector designed for detection outdoors with a wide 
angle, volumetric differential field of view.  It incorporates microprocessor-controlled signal processing including 
signal shape analysis, adaptive threshold level by feedback of environmental effects, temperature compensation 
and rejection of disturbance signals. 
Sensitivity adjustments are done with DIP-Switches for each individual unit in function of the required detection 
range in order to adapt to the specific needs of an installation. 

2 Features 

„

 

Multi Zone Volumetric with Creep Zones 

„

 

4 Meter (13 Feet) Mounting Height 

„

 

Advanced Tamper Detection 

„

 

Low Power Consumption – Ideal for Wireless and Solar Applications 

„

 

Wide Power Supply Range 

„

 

Integrated Bracket for Wall Mounting 

3  Mounting and Installation 

The mounting structure should be sold enough to resist significant movement in windy conditions.  Movement of the 
VID-W20L030 caused by vibrations or other movements will result in changing fields of view covered by the VID-
W20L030 and could cause erratic signals.  These unwanted signals may lead to an increase in the alarm threshold 
level which reduces the detection probability or in certain cases can lead to unwanted alarms. 
The stainless steel bracket is ideally suited for wall mounting.  For pole mounting the VID-PA is available (the pole 
mount bracket comes with two strap bands for poles with diameters of 4 – 16cm).  For further information please 
refer to 16.2. 

It is very important that the cover of the detector is tightened securely.  Tighten the two screws to the point where 
it cannot be tightened further with reasonable force.  There should be less than 1mm gap between the cover and 
the bottom part of the housing. 

The detectors are fitted with two M16 cable entry points.  The nut on the cable entry assembly should be tightened 
to clamp the cable in place.  If the cable diameter is too small to be held properly, insulation tape should be wound 
around the cable to increase the outside diameter to a suitable size. 

4  Connecting the VID-W20L030 

For the definition of the electronic board and terminal block see appendix 19.1. 

5 Alarm 

Signalling 

There are two types of alarm outputs on the VID-W20L030: 

 

one SPST potential-free relay contact   

 

one open collector transistor output 

Cover Switch 

A tamper detection switch is fitted for the cover, this contact opens when the cover is opened. 

6  Field of View 

The VID-W20L030 has a volumetric field of view with differential detection areas.  For the nominal range and width 
at that range see table below. 

7 Alignment 

The detection range of a PIR detector is not limited but it is a function of the target size, speed and temperature 
contrast against its background.  The VID-W20L030 should be aligned so that a natural or artificial background at 
the end of the range terminates the field of view. 
Vertical alignment is optimal when the upper edge of the field of view is at 1.5 to 2.5m (5 to 8 ft) above ground at 
the end of the required detection range.  Use the grove on the top of the detector for correct alignment.  This line of 
sight corresponds to the upper edge of the detection pattern.  To limit the detection range, a terminating screen can 
be used to prevent detection of targets beyond the required range. 

Definition VID-W20L030 

Nominal Range 

30m (100 feet) 

Width at Nom. Range 

20m (65 feet) 

Summary of Contents for VID-W20L030

Page 1: ...Manual VID W20L030_1 2008 doc page 1 10 www norbain co uk Installation Manual VID W20L030 Vista Infra Red Detector Medium Range Volumetric A Detector for Outdoor Perimeter Protection...

Page 2: ...ange 4 7 2 Horizontal alignment of VID W20L030 4 8 Sensitivity Settings 4 9 Adaptive Threshold Discrimination ATD 5 10 Pulse Count 5 11 Test 5 12 Anti Vandal Function AVF 5 13 LED 6 14 Alarm Time 6 15...

Page 3: ...htened securely Tighten the two screws to the point where it cannot be tightened further with reasonable force There should be less than 1mm gap between the cover and the bottom part of the housing Th...

Page 4: ...f view will reduce the sensitivity of the VID W20L030 by increasing the alarm threshold level and may also lead to unwanted alarms Top view Fig 2 The detection patterns of Fig 1 and 2 are for illustra...

Page 5: ...4 is used to set a pulse count delay for the alarm activation This means that the alarm output is only activated after a pre set number of pulses having reached the alarm criteria within a certain pe...

Page 6: ...l temperature Sufficient time should be given to the VID W20L030 to reach the correct internal temperature and sensitivity before performing walk tests During the initial period of operation it is str...

Page 7: ...D W20L030 cannot be excluded Detection is a function of thermal contrast speed and size of a target crossing the detectors field of view Contrast conditions can vary significantly in the course of the...

Page 8: ...N Not used ON OFF HW setting 100 OFF ON HW setting 75 OFF OFF HW setting 40 Function Switches SW Function 3 ATD 4 Pulse count 5 Test 6 Anti vandal function Relay shown in energised non alarm condition...

Page 9: ...cal Case Material Heavy duty plastic Colour white Weight app 900 g 2 0 lbs incl mounting bracket Cable Feeds 2 x M 16 with cable clamp Outer Cable Diameter 4 5 10 mm 0 18 0 40 inch Electrical Supply V...

Page 10: ...a reasonable opportunity to appraise the products and have made your own independent assessment of the fitness or suitability of the products for your purpose You acknowledge that you have not relied...

Reviews: