Visonic MCT-426 Installation Instructions Manual Download Page 2

2

 

D-302151 MCT-426, MCT-427 Installation Instructions

 

3.2 Audible and Visual Indications 

The dual color LED and buzzer are used to signal various alarm and 

trouble messages as shown in Table 1 below: 

Table 1. 

Visual and Audible Indications 

Condition

 

Visual Indication (LEDs)

 

Audio 

Indication 

Red

 

Yellow

 

Smoke alarm

 

Flash every 

500ms 

 

-

 

3 long beeps every 

4 sec. 

Heat alarm(***)

 

Flash every 

500ms

 

-

 

Long beep every 

2 sec. 

Tamper 

alarm(*)

 

-

 

-

 

Long beep every 

2 sec. 

Standby 

 

Flash every 30 

sec.

 

-

 

Low battery

 

Flash every 30 

sec.

 

-

 

Short beep every 

30 sec. 

Smoke sensor 

trouble

 

Flash every 60 

sec.

 

3 Flashes every 

60 sec.

 

Short beep every 

60 sec. 

Low sensitivity 

alarm

 

Flash every 30 

sec.(**)

 

-

 

Short beep every 

30 sec. 

Heat sensor 

trouble(***)

 

Flash every 60 

sec.

 

5 Flashes every 

60 sec.

 

Short beep every 

60 sec. 

Need to clean

 

2 flashes every 

30 sec.

 

-

 

2 short beeps 

every 30 sec. 

Test

 

See par. 3.7 

The tamper alarm will mute for 3 minutes at first power on, and 

will revert to normal mode when the tamper switch condition is 

changed. 

**  Delay of 15 sec. between buzzer beep and LED operation 
***   MCT-427 only 

3.3 Battery Connection and Initial Test 

Attention: 

The detector battery cover is fitted with a red button that 

prevents the detector from locking onto bracket if there is no battery 

inside.  

The smoke detector is supplied with a 3V CR123A / CR17450 battery. 

Battery connection for both types of batteries is illustrated in Figure 3a 

and 3b below. 

Battery cover

Open battery cover and

connect the battery to its

t e r m i n a l s   ( w i t h o u t

insulator). Verify proper

polarity.

3 volts CR123A

Tamper

switch

Transmission

LED ON/OFF

button

 

Figure 3a.

 

Battery Connection for CR123A 

 

Battery cover

Open battery cover and connect the battery to its terminals.

3 volts CR17450

Tamper

switch

Transmission

LED ON/OFF

button

 

Figure 3b.

 

Battery Connection for CR17450

 

Note:

 When the battery first makes contact, the alarm horn may 

sound for one second. This indicates that the battery is connected 

properly.  

Close the cover, then press the test button (see fig. 1) for about 5 

seconds, (for further details see par. 3.6).

 

3.4 Resetting the Transmitter Module 

and Enrolling its PowerCode ID 

The detector has a wall / rear tamper switch to alert removal of 
detector. The tamper switch actuator, extending through a hole in the 
base (see Figure 3), is pressed against the bracket when the unit is 
attached to the bracket. 
Removal of the unit from the bracket will cause the switch contacts to 

open, creating a tamper event, which will be reported by the transmitter 

to the control panel.   
Refer to the control panel’s installation instructions and follow the 

procedure given there for enrolling transmitter IDs in the control panel's 

memory.  
When required to initiate a transmission for enrollment, press the smoke 

detector’s test button (see fig. 1) until the built-in horn sounds, or press 

the tamper switch. 

Note:

 It is much easier to carry out this operation while holding the 

MCT-426 / MCT-427 in your hand, close to the control panel.

 