Visonic MC-302E PG2 Installation Instructions Download Page 2

D-303384 MC-302E PG2 Installation Instructions 

WARNING!

 To comply with FCC and IC RF exposure 

compliance requirements, the magnet contact device should be 
located in a distance of at least 20 cm from all persons during 
normal operation. The antennas used for this product must not 
be co-located or operated in conjunction with any other antenna 
or transmitter. 

1.

  Insert a flat-edged screwdriver into 

the slot and push upward to 

remove cover. 

2.

 Remove screw 

3.

 Separate base from cover.  

4.

 Flex catch and remove P.C. board  

5.

 Mark & drill 2 holes in mounting 

surface. 

Fasten base with 2 countersunk 

screws. 

6.

 Mount the magnet near its location 

mark with 2 screws 

A.

 Enroll button 

B.

 Fixed frame 

C.

 Moving part 

 

Figure 3b.

 Mounting

 

 

2.2 Auxiliary Input Wiring 

(Fig. 4)

 

A

. Connect the auxiliary sensor contacts across the MCT-302E auxiliary 

input terminals. 

B.

 If the auxiliary input of the MCT-302E PG2 is defined as a Normally 

Closed (N.C.) type, series connected N.C. sensor contacts must be 
used exclusively. An E.O.L. resistor will not be required.

 

 

Figure 4.

 E.O.L. Wiring Example 

C.

 If the auxiliary input of the MCT-302E PG2 is defined as a Normally Open (N.O.) type, parallel connected N.O. sensor contacts must 

be used exclusively. An E.O.L. resistor will not be required.

 

D.

 For E.O.L. supervision:

 

Normally Closed (N.C.) sensor contacts can be used, as shown in Figure 4. A 47k

 E.O.L. resistor must be wired at the far end of the 

zone loop. 

Note:

 For UL installations, the device connected to the initiating circuit must be located in the same room as the transmitter. 

The drawing below illustrates a N.O. and N.C. alarm circuit with E.O.L. resistor. 

Note: 

An alarm message is transmitted once the loop is opened or short circuited. 

2.2. Enrollment 

Refer to the PowerMaster panel's Installer Guide and follow the procedure under the 

"

02:ZONES/DEVICES

"

 option of the Installer Menu. 

A general description of the procedure is provided in the following flow chart.

 

Step 1

 

Step 2

 

Step 3

 

Step 4

  

 

Step 5

 

Step 6

Enter the Installer menu 

and select 

02:ZONES/DEVICES

 

Select "

ADD NEW  

DEVICE

" Option  

See Note [1] 

Enroll the device or Enter 

the device ID

 

Select the desired Zone 

Number 

Configure Location, 

Zone Type & 

Chime Parameters

 

Configure 

the 

Magnet 

 

 

 

 

 

 

 

 

 

 

means scroll

 

 

and select

 

 

  

 

 

 

See Note 

[2]

 

Notes:

  

[1] If the magnetic contact device is already enrolled you can configure the magnetic contact device parameters via the 

“Modify Devices” 

option 

– see Step 2. 

[2]

 

Select the 

"Device Settings"

 option and refer to section 2.3 to configure the magnetic contact device parameters

2.3. Configuring the Magnetic Contact Device Parameters 

Enter the 

 

menu and follow the configuration instructions for the MC-302E PG2 magnetic contact device as described in the 

following table. 

Option 

Configuration Instructions 

 

 

Determine whether or not the alarm LED indication will be activated.

 

Optional settings: 

 LED Enabled

 or 

LED Disabled

 (default). 

 

 

 

 

 

Determine whether to enable or disable the internal reed switch.

 

Optional settings: 

 Enabled

 or 

Disabled

 (default). 

 

 

 

 

Define the external input according to the installer's requirements.

 

Optional settings: 

Disabled

EOL-End Of Line

 (default), 

Normally Open

 or 

Normally Closed

 

 

 

 

 

 

 

 

Input #1

 

Reed Switch #1

 

Alarm LED

 

DEVICE SETTINGS

 

Z06.DEV SETTINGS 

Z06.SET CHIME 

Z06.ZONE TYPE 

Z06.LOCATION 

ID No. 101-XXXX 

Z06:Contact Sens 

ENTR ID:XXX-XXXX 

ENROLL NOW or 

MODIFY DEVICES 

ADD NEW DEVICES 

02.ZONES/DEVICES 

Reviews: