Visonic K-940MCW Installation Instructions Download Page 2

DE3635

 

 

Figure 3.

 Components Layout

  

3.2 Enrolling the Transmitter ID in the 

Target Receiver’s Memory 

Refer to the target receiver’s installation instructions and follow the 
procedure given there for “teaching” transmitter IDs. It is much 
easier to carry out this operation in close proximity to the receiver. 

3.3 Selecting the Mounting Location  

The K-940MCW can be mounted directly onto the wall (surface 
mounted), or in a corner, using the mounting knockouts. Always 
mount the unit on a firm and stable surface. Optional swivel 
brackets permit greater flexibility when directing the detector at a 
desired point (Para. 3.8).  

A.

  Select the mounting location so that an intruder's motion will 

be perpendicular to the detector’s coverage pattern. 

B.

  You may mount the unit at the height of 1.8 m (6 ft), or 2.1 m 

(7 ft), or 2.4 m (8 ft).  

 

Important!

 The detector is immune to 18 kg 

(40 lb) animals moving on the floor or 
climbing on furniture as long as the activity 
takes place below 1 m (3 ft). Above the 1 m 
(3 ft) height limit, the detector is immune to  
9

 

kg

 

(20

 

lb)

 

pets, but

 

the

 

pet

 

immunity

 

will

 

decrease as the pet gets closer to the detector. It is therefore 
recommended to select a mounting location that minimizes 
potential close proximity of animals. 

These characteristics have not been verified by UL.

 

C.

  To minimize false alarms, avoid aiming the detector at heaters, 

sources of bright light, or windows subjected to direct sunlight. 

D.

  The PIR detector senses the difference between the infrared 

energy transmitted by a moving body and the background 

temperature. It is therefore recommended that the PIR be 

aimed toward the coolest place in the protected area, in order 

to obtain the maximum sensitivity in installations where high 

background temperatures are expected. 

3.4 Direct Mounting 

A.

  Loosen and remove the screw at the bottom of the case and 

take the cover off. 

B.

 Punch out the appropriate mounting knockouts in the base. 

 

Note: 

For wall surface mounting, use the two elongated 

knockouts at the middle of the base. For corner mounting, use 
two diagonally opposite knockouts at the angled sides of the 
base (see Figure 3). 

 

C.

  Loosen the vertical adjustment screw, slide the printed circuit 

board upward and remove it via the “keyhole”. 

D.

  Use the base as a template for marking the drilling points. 

E.

   Drill mounting holes and insert masonry anchors if required. 

F.

   Mount the base in place using two screws. 

G.

 Remount the PC board and secure it with the vertical 

adjustment screw. 

3.5 Vertical Adjustment  

A. Pet-Immune Applications

 

 

To maintain maximum coverage range and 
pet immunity, the vertical adjustment scale 
must be adjusted in accordance with the 
actual mounting height (refer to Figure 4). 
Loosen the vertical adjustment screw

 

and

 

slide the printed circuit board up or down until

 

the pointer shows the actual mounting height on the scale. 
When done, re-tighten the screw well. 

 

Figure 4.

 Vertical Adjustment

 

B. Pet-Free Locations

 

 

To obtain the best coverage possible where no pets are present, 
mount the detector with a swivel bracket (see Para. 3.8) at any 
desired height between 1.8 m (6 ft) and 2.4 m (8 ft). Then set the 
vertical adjustment scale 

to the 2.4 m (8 ft) position

 and use the 

bracket to tilt the detector 30° down. 

3.6 Setting the Pulse Counter  

K-940MCW detectors are equipped with a programmable pulse 

counter which can be set to count 1, 3 or 5 pulses, before 

activating the wireless transmitter. 

The factory default is 3 

pulses

. Place the pulse count jumper at the desired setting (1, 3 

or 5 - see Figure 5).  

 

Figure 5. 

Setting the Pulse Counter 

3.7 Walk Testing 

The K-940MCW is equipped with a LED/WALK TEST jumper 
which is set by default to ON. In this default position, the 
LED lights for 2 seconds upon transmission by the unit.

 

To save battery power in normal use, an automatic timer inhibits 
the detector for approximately 2 minutes after transmitter 
activation. The detector is automatically rearmed 2 minutes after 
detection of the last motion. 

For effective walk testing, it is necessary to override 
the 2 minute timer by setting the LED/WALK-TEST 
jumper to the TEST position as shown to the right. 

 

 

Reviews: