Vision V700-T20BJ Installation Manual Download Page 4

 

Vision™ Installation Guide  

 

 

Unitronics 

 

 

Inserting the Battery 

In order to preserve data in case of power-off, you must insert the battery.

 

The battery is supplied taped to the battery cover on the rear of the controller.

 

1. Remove the battery cover shown on page 3.  

The polarity (+) is marked on the battery holder and on the battery. 

2. Insert the battery, ensuring that the polarity symbol on the battery is: 

- facing up  
- aligned with the symbol on the holder 

3. Replace the battery cover. 

 

  Use proper precautions to prevent Electro-Static Discharge (ESD) while servicing the 

battery.  

Caution 

  To preserve back-up values for RTC and system data during battery replacement, the 

controller must be powered. 

 

Wiring 

 

  Do not touch live wires. 

 

  Install an external circuit breaker. Guard against short-circuiting in external wiring. 

  Use appropriate circuit protection devices. 

  Unused pins should not be connected. Ignoring this directive may damage the device. 

  Double-check all wiring before turning on the power supply. 

Caution

 

  To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm). 

  Do not use tin, solder, or any substance on stripped wire that might cause the wire  

strand to break. 

  Install at maximum distance from high-voltage cables and power equipment. 

 

 

 

 

 

Wiring Procedure 

Use crimp terminals for wiring; use 3.31 mm² 

–0.13 mm² wire (12-16 AWG): 

1. Strip the wire to a length of 7±0.5mm (0.270

–0.300“). 

2. Unscrew the terminal to its widest position before inserting a wire.  

3. Insert the wire completely into the terminal to ensure a proper connection. 

4. Tighten enough to keep the wire from pulling free. 

  Input or output cables should not be run through the same multi-core cable or share the same wire. 

  Allow for voltage drop and noise interference with I/O lines used over an extended distance.  

Use wire that is properly sized for the load. 

  The controller and I/O signals must be connected to the same 0V signal. 

   

   

   

Summary of Contents for V700-T20BJ

Page 1: ...s and General Restrictions When any of the following symbols appear read the associated information carefully Symbol Meaning Description Danger The identified danger causes physical and property damag...

Page 2: ...ccordance with the standards given in the product s technical specification sheet Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation...

Page 3: ...er into the cut out ensuring that the rubber seal is in place 3 Push the mounting brackets into their slots on the sides of the panel as shown in the figure below 4 Tighten the bracket s screws agains...

Page 4: ...s Unused pins should not be connected Ignoring this directive may damage the device Double check all wiring before turning on the power supply Caution To avoid damaging the wire do not exceed a maximu...

Page 5: ...n and ground connection directly to the earth ground of your system For ground wiring use the shortest and thickest possible wire Communication Ports The controller comprises a USB port 1 RS232 RS485...

Page 6: ...5 Pin 1 DTR is used for signal A and Pin 6 DSR signal is used for signal B RS232 to RS485 Changing DIP Switch Settings The port set to RS232 by factory default To change the settings first remove the...

Page 7: ...pply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly aligned Removing a Snap in I O Module 1 Locate the four b...

Page 8: ...limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in the information presented in t...

Reviews: