McQuay IM 672-7
27
Operation
Figure 41: Torque for FC Variable Inlet Vanes (in.–lb.)
Figure 42: Torque for AF Variable Inlet Vanes (in.–lb.)
300
250
200
150
100
90
80
70
60
50
350
400
450
500
550
600
650
700 750 800 850
900
1000
1500
2000
Fan speed (rpm)
FC22.25
FC20.00
FC18.00
FC15.00
FC12.62
FC24.50
T
orque (in–lb)
300
250
200
150
100
600
650
700
750
800 850
1000
Fan speed (rpm)
900
400
350
550
900
AF40.25
AF27.00
AF24.50
AF22.25
AF20.00
AF38.50
AF33.00
AF30.00
500
600
700
800
2000
1000
1500
1500
2000
3000
2500
T
orque (in–lb)
Table 12: Operating Limits—Plenum Fans
Fan operating limits
Plenum fans
Diameter
13.5
15
16.5
18.25
20
22.25
24.5
27
30
33
36.5
40.25
44.50
49
54.25
60
Max. rpm Class I
2895
2589
2376
2256
2077
1875
1691
1479
1328
1209
1073
972
882
799
725
651
Max. rpm Class II
3786
3384
3100
2959
2703
2413
2199
1928
1730
1579
1401
1264
1150
1043
938
847
Max, rpm Class III 4000
4000
3887
3735
3409
3065
2780
2423
2182
1984
1756
1598
1447
1314
1178
1071
Table 13: Operating Limits—Inline Fans, Twin Fans
Fan operating limits
Inline fans/Twin fans
Diameter
18.25
20
22.25
24.5
27
30
33
36.5
40.25
44.50
49
54.25
Max. rpm Class I
2727
2488
2236
2041
1835
1665
1476
1330
1208
1072
973
880
Max. rpm Class II
3409
3111
2796
2551
2294
2082
1846
1662
1510
1340
1216
1100
Twin fans
Dia.
9 x 9
10.62
12.62
15
18.12
20
Max. rpm
2575
2400
2000
1700
1400
1200
Max. hp
10
15
15
30
40
40