ESTAmat PFC-N
D.No.13157 - Rev. 02
Operating Instruction MV1181
Page 5 of 36
Operation of ESTAmat PFC-N
in High Voltage compensation panels
The below list is showing the parameters of the ESTAmat PFC-N which
need special attention for operation in High Voltage compensation
panels.
Attention: When putting the ESTAmat PFC-N in operation, the
countdown for “AI” has to be stopped by pushing the “esc”
button.
Un = Adjust the nominal voltage to local conditions
Ct = Adjust the Ct ratio to local conditions
Pt = Adust the Pt ratio to local conditions
St = Adjust the switching time to local requirements
208 = Set item
208 to “No” and switch off the countdown for “AI”
308 = Set item 308 to “Yes” and switch off the automatic step size
detection.
401 = Adjust discharging time to local conditions
402 = Adjust step sizes
Attention
: When resetting the ESTAmat PFC-N by using menu
item 601 or 602, all adjusted values are set to factory settings.
When using factory settings for High voltage compensation
a proper and save operation is not possible!