Information concerning the allocation of these areas may be found in
the description of the corresponding System SLIO module.
Please consider the System SLIO power and clamp
modules do not have any module ID. These may not be
recognized by the DeviceNet coupler and so are not listed
and considered during slot allocation. Further within Devi-
ceNet the slots are designated as DeviceNet-Slot. The
counting always begins with 1.
If you do not use a DeviceNet scanner from Allen-Bradley as long as
you change the System SLIO module configuration, you should acti-
vate the auto configuration. To activate the Auto configuration switch
the DIP switch A of the address switch to "1" before switching on the
power supply. To store the module configuration, switch the DIP
switch A of the address switch to "0".
When used with a DeviceNet scanner from Allen-Bradley if the config-
uration of the modules has been changed, the coupler must be
advised to take the new configuration. For this one of the following
actions must be executed otherwise an error is reported:
n
Reading the device name of a installed module
(Class Code 101 ... 164, Instance 1)
n
Reading respectively writing of a parameter character of a
installed module
(Class Code 101 ... 164, Instance 20)
Note to the assignment
of the module configu-
ration
VIPA System SLIO IM 053DN
Deployment
Accessing the System SLIO
HB300 | IM | 053-1DN00 | GB | 15-33
41