Chapter 3 Deployment CPU 21x
Manual VIPA CPU 21x
3-6
HB103E - Rev. 05/45
Project engineering
The following information always refers to modules that have been installed
on the same bus adjacent to the CPU.
In order to address the installed peripheral modules individually, specific
addresses in the CPU have to be assigned to them.
The allocation of addresses and the configuration of the installed modules
is a function of the Siemens SIMATIC Manager where the modules appear
as a virtual Profibus system. For the Profibus interface is software
standardized, we are able to guarantee the complete functionality of the
System 200V together with the Siemens SIMATIC Manager by including a
GSD-file (german:
G
eräte
S
tamm
D
atei = GSD-file).
The project is transferred serial to the CPU via the MPI interface or by use
of a MMC.
For the employment of the CPU 21x from VIPA using the Siemens
SIMATIC Manager the inclusion of the System 200V via the vipa GSD file
in the hardware catalog is required.
To be compatible with the Siemens SIMATIC Manager you have to execute
the following steps:
•
Start the hardware configurator from Siemens and include vipa_21x.gsd
from VIPA.
•
Configure CPU 315-2DP (315-2AF03 0AB00 V1.2) from Siemens and
create a new Profibus subnet.
•
Attach the System "VIPA_CPU21x" to the subnet with
Profibus-
Address 1
, to be found at the hardware catalog at
PROFIBUS DP
>
Additional field devices
>
IO
>
VIPA_System_200V
.
•
Place
always at the 1
st
slot
the corresponding CPU 21x, by taking it
from the hardware catalog.
•
Include afterwards your System 200V modules in the location sequence.
•
Save and transfer you project.
The following conditions must be fulfilled for project engineering:
•
The Siemens SIMATIC Manager is installed at PC respectively PU
•
The GSD files have been included in Siemens hardware configurator
•
Serial connection to the CPU (e.g. "Green Cable" from VIPA)
Note!
The configuration of the CPU requires a thorough knowledge of the
Siemens SIMATIC Manager and the hardware configurator!
General
Fast introduction
Requirements
Summary of Contents for CPU 21 Series
Page 1: ...Manual VIPA CPU 21x Order No VIPA HB103E Rev 05 45 ...
Page 2: ...Lerrzeichen ...
Page 6: ...About this Manual Manual VIPA CPU 21x Subject to change to cater for technical progress ...
Page 10: ...Contents Manual VIPA CPU 21x iv HB103E Rev 05 45 ...
Page 30: ...Chapter 1 Principles Manual VIPA CPU 21x 1 18 HB103E Rev 05 45 ...
Page 58: ...Chapter 2 Hardware description Manual VIPA CPU 21x 2 28 HB103E Rev 05 45 ...
Page 80: ...Chapter 3 Deployment CPU 21x Manual VIPA CPU 21x 3 22 HB103E Rev 05 45 ...
Page 178: ...Chapter 5 Deployment CPU 21x 2BT02 with H1 TCP IP Manual VIPA CPU 21x 5 48 HB103E Rev 05 45 ...