background image

                                                       

 

                       

 

- 10 -

1) Set Point 

Rotate the circular selector in correspondence with the arrow placed nearby. The 
selector represents -33°F to 50°F (-35°C to +10°C) for low temperature models, 
and 14°F to 68°F (-10°C to +20°C) for medium temperature models. “10” is the 
coldest setting, “1” is the warmest.  

 
2) Differential 

It is possible to modify the differential from 1°F minimum to 12.5°F maximum. 
Simply shift the first two dip-switches to the ON or OFF position according to the 
wanted value. 

 
3) Defrost management and setting 

A defrost can be activated manually, by pressing the “man. def.” button, or 
cyclically, the interval set by the “def.intvl” rotary switch at the top left with respect 
to Set Point selector. The interval can be selected from 1 to 12 hours in 1 hour 
steps. If the selector is positioned on the “0”, the cyclic defrost is disabled. 
 

Note: 

manual defrost reinitializes the time required for successive cyclic 

defrosting. The selections are effective beginning from the successive cycle. For 
an immediate effect, it is necessary to turn power to the UniStat off for a few 
seconds. 
It is possible to choose between an electric defrost (the compressor is 
deactivated and the defrost relay is activated) and a hot gas defrost (both the 
compressor and the defrost relay are activated); The defrost termination, can 
take place by time (from 1 to 60 min.) or by temperature (from 0 to 86°F) if the 
defrost sensor is utilized for the correct programming). If the defrost sensor is 
disconnected, interrupted or breaks down for any reason, the defrost terminates 
after a maximum time of 90 minutes if it is resistance-based, or 40 minutes if it is 
hot-gas based. 
The instrument stores the defrost state every 15 minutes to allow restart after 
power loss. 

 
4) Compressor safety function 

If the function is enabled, a minimum three minute interval is ensured between 
deactivation and successive restart of the compressor. 
If the function is enabled, the compressor is not energized for three minutes after 
controller power up. 
The function is also active in hot-gas defrost mode. 
 

 
 
 
 
 
 
 

Summary of Contents for WINE-MATE WM-4500SSH

Page 1: ...Split System Installation Operation Care Manual WM 2500SSH 4500SSH WM 6500SSH 8500SSH V Vi in no ot te em mp p I In nt te er rn na at ti io on na al l C Co or rp p w ww ww w v vi in no ot te em mp p c...

Page 2: ...1 TABLE OF CONTENTS Important Safety Information 2 Feature Description 3 Installation Instruction 5 Use and Temperature Control 9 Care Guide 11 Troubleshooting 12 Customer Support 14 Warranty 15...

Page 3: ...2 Important Safety Information DO NOT USE A GROUND FAULT INTERRUPTER GFI A DEDICATED 20 AMPCIRCUIT IS HIGHLY RECOMMENDED...

Page 4: ...frigerated enclosure as far as 50 feet which will bring you extremely quiet operation The dimension and capacity are specified as follows Model Capacity Btu h 55 90 F Unit Cooler Cond Unit Electrical...

Page 5: ...4 Evaporator Unit Condensing Unit...

Page 6: ...nd shaded from direct sun It should not be exposed to temperatures higher than 125 F or lower than 20 F Air flow from the unit cooler should be unobstructed for at least 1 foot 2 Refrigeration Install...

Page 7: ...te and charge system with R134A Refrigerant amount will vary depending on the length of line set 3 Air Sensor The air sensor is recommended to place in the wine room If it is in a return duct the temp...

Page 8: ...ack white and green wires that come from the cooling unit in the electrical terminal Remove the electrical box and mount it close to the wine room so the air sensor can reach the wine room Use extra w...

Page 9: ...8 6500SSH Electrical Wiring Diagram 8500SSH Electrical Wiring Diagram...

Page 10: ...wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize...

Page 11: ...s are effective beginning from the successive cycle For an immediate effect it is necessary to turn power to the UniStat off for a few seconds It is possible to choose between an electric defrost the...

Page 12: ...need to be cleaned at least every 6 months Unplug the system or disconnect power Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty Plug cooling system or re...

Page 13: ...or condenser fan f Clean condenser g Call service for removing refrigerant h Call service for OEM information 3 Fan motor running but compressor not running a Incorrect power supply b Incorrect or loo...

Page 14: ...t wirings c Failed components a Check for proper fuse or breaker b Check for wirings and connections c Call service 8 Noisy operation a Mounting area not firm b Loose parts c Compressor overloaded due...

Page 15: ...14 Customer Support If you still have problems please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com...

Page 16: ...ies express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products s...

Page 17: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...