background image

                                                       

 

                       

 

- 3 -

Cellar Construction 

 
This is only a guide and shall be considered as minimum requirements. 
 
All interior walls and floors shall have a vapor barrier and a minimum of R13 
insulation. All exterior walls and ceiling shall have a vapor barrier and a minimum 
of R19 insulation. The vapor barrier shall be installed on the warm side of the 
insulation. All joints, door frames, electrical outlets or switches and any pipes or 
vents that go through the cellar shall be sealed to prevent air and moisture 
leakage into the cellar. Concrete, rock, and brick are not insulation or vapor 
barriers. 
 
Doors shall be of a minimum size, insulated to at least R13 and tightly sealed 
with high quality weather stripping. Be sure to seal the bottom of the door and fill 
gap between the door’s frame and wall before installing the cap molding.  
In order to maintain 55 °F in the wine cellar, the ambient temperature 
surrounding the enclosure shall not exceed the temperature of the cellar by more 
than 25 °F. No cellar wall shall receive direct sun or strong wind.  
 
Lighting shall be of low wattage, with a timer to insure lights are not left on when 
the cellar is not occupied.  
 
The cooling system will not be able to maintain the proper temperature if fresh 
moisture-laden air is constantly being introduced to the cellar. Symptoms of this 
condition are; cooling unit runs all the time with only a slight reduction in 
temperature and/or water overflows from the unit. Because of the temperature 
difference between the inside and outside, very small cracks can allow large 
amounts of outside air to enter into the cellar. Please be aware that moisture can 
pass through solid concrete, paint and wood. Often a newly constructed cellar 
contains fresh wood, paint, concrete and other building materials. These 
materials contain large amounts of moisture. When placed into operation in this 
type of environment, the system will work harder to remove this extra moisture 
resulting in increased “run” time. 

 
 
 
 
 
 
 
 
 
 

 
 
 

Summary of Contents for Wine-Mate WM-2520SSV

Page 1: ...co om m Rack Split Cooling System Installation Operation Care Manual WM 2520SSV WM 4520SSV WM 6520SSV w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he es se e...

Page 2: ...1 Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 10 AMP circuit for WM 2520SSV and 15 AMP for WM 4520 6520SSV are required...

Page 3: ...le of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 25 Customer Support 28 Warran...

Page 4: ...erature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer...

Page 5: ...cellars 50 ft so that noise and compressor vibration are isolated SSV evaporator units are designed for installation inside a rack or in a wine room corner making them an ideal choice for small and m...

Page 6: ...eight lb Evap Unit Cond Unit WM 2520SSV WM 252SFCV WM 252SCU 18x14x12 2100 180 230 R134a 220V 50Hz 0 4A 220V 50Hz 3A 45 40 WM 4520SSV WM 452SFCV WM 452SCU 18x14x12 3700 280 900 R134a 220V 50Hz 0 4A 22...

Page 7: ...o lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock t...

Page 8: ...etting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setti...

Page 9: ...lar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 9 How to set low cellar temper...

Page 10: ...elay min 1 ot probe calibration 0 US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative...

Page 11: ...lean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Removing...

Page 12: ...temperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it...

Page 13: ...st side and leave minimum 1 foot clearance for the ambient air intake side c Check for excessive size d Check for installation location e Clean condenser f Check for fan and air short circulation 8 Co...

Page 14: ...leak No water overflow but water leak a Check for any air leak b Use drain line c Check supply air flow or air TD crossing evaporator d Clean the drip tray e Seal the leak using silicone sealant 15 Co...

Page 15: ...building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized...

Page 16: ...15 CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 252 652SFCV Evaporator Unit...

Page 17: ...16 Fig 4 WM 252 452SCU Condensing Unit Fig 5 WM 652SCU Condensing Unit...

Page 18: ...A grille can be used to cover the supply and return with 0 2 clearance or 2 3 ft long duct can be added 4 There is a gravity drain system used so the unit shall be installed level or with a slight slo...

Page 19: ...5 ft clearance for the exhaust side and leave minimum 1 foot clearance for the ambient air intake side 4 Service valve operations 1 Process Manometer 2 Receiver Discharge or Compressor Suction 3 Liqu...

Page 20: ...rculated 3 Air probe can be pulled out of the temperature controller around 5 ft if additional wires are needed 18 gauge wires may be used to extend the air probe 5 Checking Control Settings 1 Use of...

Page 21: ...ntrol Head pressure setting Cut in 170 psig Cut out 120 psig Differential 50 psig It closes on rise of pressure It may need to adjust the setting in the field to avoid fan short cycle Fig 13 Condenser...

Page 22: ...difference is more than 10 ft or the line set exceeds 75 ft use both inverted U trap and suction accumulator 3 If the condensing unit is located more than 10 ft above the evaporator unit use U trap t...

Page 23: ...peed position then rotate the setting located on the side or front clockwise to decrease the minimum speed or counter clockwise to increase the minimum speed The minimum speed should be adjusted until...

Page 24: ...heat and low subcooling 3 High suction pressure and high head pressure Low superheat and high subcooling 4 High to normal suction pressure and high head pressure Low subcooling 5 High suction pressure...

Page 25: ...nd high subcooling evaporator iced 11 Evaporator restricted 12 Expansion valve restricted 13 Both evaporator and condenser restricted liquid and suction lines connected wrong 14 Liquid line restricted...

Page 26: ...are the field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the co...

Page 27: ...26 Fig 17 WM 6520SSV Electrical Wiring Diagram Fig 18 Low Ambient Temperature WM 2520 4520SSV LA Electrical Wiring Diagram...

Page 28: ...27 Fig 19 Low Ambient Temperature WM 6520SSV LA Electrical Wiring Diagram...

Page 29: ...8 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp co...

Page 30: ...ties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products...

Page 31: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...

Reviews: