-16-
Parts not included:
Liquid line copper tubing
Suction line copper tubing
Water lines
CAUTION
Liquid and suction line locations may differ from that they are shown
below, please check on the units for proper installations.
NOTE
To prepare rough-in, leave minimum
4” clearances for electrical
wiring and refrigeration piping.
Model No.
Evap Unit
W” x D” x H”-
A”xB”
Cond Unit
L” x W” x
H”
Electrical Rating
Evap Unit / Cond
Unit
Min Circuit
Ampacity
Weight (lb) Evap
Unit / Cond Unit
WM-
2500SSLWC
WM-25SFCL
31.75 x 14.5 x
4.75-
29.75 x 14.75
WM-
250SCUR-
WC
24 x 18 x 18
115V-60HZ-1A
115V-60HZ-5A
20A
29 / 40
WM-
4500SSLWC
WM-45SFCL
40.25 x 14.5 x
4.75-
38.25 x 14.75
WM-
450SCUR-
WC
24 x 18 x 18
115V-60HZ-1A
115V-60HZ-6A
20A
37 / 60
WM-
6500SSLWC
WM-65SFCL
53.75 x 16.5 x
6.75-
51.75 x 16.75
WM-
650SCUR-
WC
24 x 18 x 18
115V-60HZ-2A
115V-60HZ-12A
30A
61 / 90
WM-
8500SSLWC
WM-85SFCL
64.25 x 18.25 x 9-
53.25 x 19.3125
WM-
850SCUR-
WC
24 x 18 x 18
115V-60HZ-2A
115V-60HZ-15A
30A
80 / 115
Fig. 3 Temperature Controller
(4.5”L X 4.5”W X 3.75H)