background image

                                                       

 

                       

 

- 23 -

7)  If the superheat is high, check the subcooling first to know if the refrigerant 

charge is sufficient. If the charge is not sufficient, add more refrigerant. If the 
charge is good, then increase the evaporator suction pressure by turning the 
hex nut (5/16”) clockwise. Liquid must always be charged into the hide side 
when the compressor runs. 

8)  If the superheat is low, then decrease the evaporator suction pressure by 

turning the hex nut (5/16”) counter-clockwise. 

9) Both discharge and suction valves must be in the back positions before 

disconnecting. 

10) Close all service valves and disconnect all manifolds and hoses. 
 

 

 

Fig. 15 Expansion Valve 

 

10. Pressure, Superheat and Subcooling Readings 

 

CAUTION:  
To read properly the service valves must be in the middle positions. 
 
 

Complaint Possible 

Causes 

1)  High suction pressure and low head pressure 

Zero superheat and zero subcooling  

2)  High suction pressure and low head pressure 

Low superheat and low subcooling 

3)  High suction pressure and high head pressure 

Low superheat and high subcooling 

4)  High to normal suction pressure and high head 

pressure 
Low subcooling 

5)  High suction pressure and high head pressure 

Low superheat and low subcooling 

6)  High suction pressure and high head pressure 

High superheat  

7)  Low suction pressure and low head pressure 

High superheat and low subcooling 

8)  Low suction pressure and low to normal head 

pressure 
High superheat and high subcooling 

9)  Low suction pressure and low head pressure 

1)  Compressor may be bad 

 

2) Expansion valve opened, too 

much oil 

3) Overcharge 
 
4) Non-condensable 

gas 

 
 
5) Air restricted, dirty condenser, 

bad condenser fans 

6) High cellar temperature, high 

evaporator load 

7) Undercharge 
 
8) 

Liquid line restricted after 
receiver, solenoid valve restricted 
 

9)  Suction line restricted 

Summary of Contents for WINE-MATE WM-2500SSH

Page 1: ...m m Duct Split Cooling System Installation Operation Care Manual WM 2500SSH WM 4500SSH WM 6500SSH WM 8500SSH w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he es se e i in ns st tr ru uc ct ti io on ns s ...

Page 2: ... 1 Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 20 AMP circuit for WM 2500SSH and 30 AMP for WM 4500 8500SSH are required ...

Page 3: ...ble of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 25 Customer Support 29 Warranty 30 ...

Page 4: ...perature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer to insure lights are not left on when the cellar is not occupied The cooling system will not be able to maintain the proper temperature if fresh moisture laden air is constantly being introduced to t...

Page 5: ...ed away from the evaporator unit 50 ft so that noise and compressor vibration are isolated SSH evaporator units are designed to provide chilled air to wine a cellar through ducts and can be located up to 25 ft away to reduce noise It also provides more installation flexibility Fig 1 SSH Duct Split Cooling System NOTE Capacity is determined under the cellar the cellar ambient and the condensing uni...

Page 6: ...500SSH WM 25SFCH 22 5x15 875 x14 375 11 WM 250SCU 18x14x12 2500 220 250 R134a 115V 60HZ 0 8A 115V 60HZ 5 7A 35 40 WM 4500SSH WM 45SFCH 25 125x22 875 x16 375 18 WM 450SCU 18x14x12 4500 380 1000 R134a 115V 60HZ 1 8A 115V 60HZ 6 9A 45 60 WM 6500SSH WM 65SFCH 25 125x22 875 x20 375 18 WM 650SCU 24x18x18 6500 490 1500 R134a 115V 60HZ 1 8A 115V 60HZ 12A 55 90 WM 8500SSH WM 85SFCH 27 125x22 875 x22 375 18...

Page 7: ...To lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys press up down keys until PON is displayed 3 Display During normal operating conditions the display shows the value measured by the air regulation probe In case of active alarm the temperature...

Page 8: ...Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize the temperature for each new temperature setting operation 3 How to see temperature set point 1 Press and immediately release the SET key th...

Page 9: ...llar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 9 How to set low cellar temperature heater The heater turns on at set point SAA minus regulation differential Shy the heater turns off at heater set point SAA NOTES Use a forced air heater to warm up the wine cellar If there is a...

Page 10: ...delay min 1 ot probe calibration 0 US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative to set point ALU high temperature alarm 10 ALL low temperature alarm 10 AFH alarm recovery differential 5 ALd temperature alarm delay min 60 dAO temperature alarm delay on startup hr 23 SAA heater s...

Page 11: ...Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Removing Remove the excessive condensate if it is accumulated in the wine cellar at high humidity conditions ...

Page 12: ... temperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost cycle and turns off at 55 F of air temperature The average air temperature is 57 F and then the wine temperature is around 57 0 5 F The air is light enough to change...

Page 13: ...ust side and leave minimum 1 foot clearance for the ambient air intake side c Check for excessive size d Check for installation location e Clean condenser f Check for fan and air short circulation 8 Condenser fan running but compressor not running a Incorrect or loose wirings b Failed components c Liquid refrigerant in the compressor a Check all wirings and connections b Check start relay start ca...

Page 14: ... leak No water overflow but water leak a Check for any air leak b Use drain line c Check supply air flow or air TD crossing evaporator d Clean the drip tray e Seal the leak using silicone sealant 15 Condensate inside ducts a Drain line restricted b Continually running not stopping c Too cold supply air a Check for drain b raise temperature setting or increase defrost cycle c Increase air flow or r...

Page 15: ...g and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the distance between the two units After the units and lines are connected the system must be checked for restriction pressurization and leak Then the system must be evacuate and charged with refrigeran...

Page 16: ... 15 CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 25 85SFCH Evaporator Unit ...

Page 17: ... 16 Fig 4 WM 250 450SCU Condensing Unit Fig 5 WM 650 850SCU Condensing Unit ...

Page 18: ... and clogged 4 There is a gravity drain system used so the unit shall be installed level or with a slight slope downward the drain connection and the drain line shall be installed slope down toward the drain If rise up is needed a condensation pump must be used 3 Condensing Unit Installation CAUTION Low ambient condition kit is required if the installation area will be below 50 F If the condensing...

Page 19: ...3 Liquid Line or Suction Line 4 Pressure Control Back Position Normal operation process and manometer port closed Front Position Liquid suction line connection closed Middle Position All ports open for evacuation charge and manometer BACK POSITION FRONT POSITION MIDDLE POSITION Fig 9 ROTALOCK Valve Operation BACK POSITION FRONT POSITION MIDDLE POSITION Fig 10 Base Valve Operation 4 Temperature Con...

Page 20: ...vaporator fans shall be running all the time Meanwhile due to the temperature differential the temperature air probe calibration should be used in order to maintain the proper wine cellar temperature 5 Checking Control Settings 1 Use of the adjustable pressure control if applicable for pump down Suction pressure setting Cut out 5 psig Cut in 25 psig Differential 20 psig Head pressure setting Cut o...

Page 21: ...he condenser fan control Head pressure setting Cut in 170 psig Cut out 120 psig Differential 50 psig It closes on rise of pressure It may need to adjust the setting in the field to avoid fan short cycle Fig 13 Condenser Fan Cycle Control B Use of the crankcase heater The crankcase heater is installed around the lower part of the compressor and shall be turned on all the time The heater is self reg...

Page 22: ... to the compressor if the elevation difference is more than 10 ft or the line set exceeds 75 ft use both inverted U trap and suction accumulator 3 If the condensing unit is located more than 10 ft above the evaporator unit use U trap to aid oil returning to the compressor 4 Complete pipe brazing check solenoid valve and expansion valve restrictions and test leak 5 Hook up the drain line and check ...

Page 23: ...to full speed with the control knob at the lowest and highest speed position To adjust the minimum speed turn control knob to the lowest speed position then rotate the setting located on the side or front clockwise to decrease the minimum speed or counter clockwise to increase the minimum speed The minimum speed should be adjusted until it supplies the required CFM Fig 14 Fan Speed Control 2 The s...

Page 24: ...Causes 1 High suction pressure and low head pressure Zero superheat and zero subcooling 2 High suction pressure and low head pressure Low superheat and low subcooling 3 High suction pressure and high head pressure Low superheat and high subcooling 4 High to normal suction pressure and high head pressure Low subcooling 5 High suction pressure and high head pressure Low superheat and low subcooling ...

Page 25: ...ssure Normal to high superheat and high subcooling 10 Air restricted at evaporator evaporator iced 11 Evaporator restricted 12 Expansion valve restricted 13 Both evaporator and condenser restricted liquid and suction lines connected wrong 14 Liquid line restricted before receiver 15 Condenser restricted 11 Condensing Unit Troubleshooting Unit not running 1 Incorrect power supply 2 Incorrect or loo...

Page 26: ... are the field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condensing unit Fig 16 WM 2500 4500SSH Wiring Diagram ...

Page 27: ... 26 Fig 17 WM 6500SSH Electrical Wiring Diagram Fig 18 WM 8500SSH Electrical Wiring Diagram ...

Page 28: ... 27 Fig 19 Low Ambient Temperature WM 2500 4500SSH LA Electrical Wiring Diagram Fig 20 Low Ambient Temperature WM 6500SSH LA Electrical Wiring Diagram ...

Page 29: ... 28 Fig 21 Low Ambient Temperature WM 8500SSH LA Electrical Wiring Diagram ...

Page 30: ...29 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com ...

Page 31: ...nties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products shall void this warranty Service under Warranty This service is provided to customers within the continental UNITED STATES only VINOTEMP cooling units are warranted to produce the stated number of BT...

Page 32: ...F USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its unit...

Reviews: