background image

                                                       

 

                       

 

- 11 -

User’s Troubleshooting 

 
This Troubleshooting Chart is not prepared to replace the training required for a 
professional refrigeration service person, not is it comprehensive. 

 

Complaint Possible 

Causes 

Response 

1. Unit not 

running

 

a.  Power cord not plugged 
b.  No power from supply 
c.  Incorrect or loose wirings 
d. Low 

voltage 

e. Setting higher than ambient 

temperature 

f. 

Cut-in too high 

g. Defrost 

light 

blinking 

h.  Compressor light blinking 
i. Defective 

controller 

a.  Check power cord 
b.  Check receptacle and fuses 
c.  Check all wirings and connections 
d.  Contact an authorized electrician 
e. Lower 

temperature 

setting 

 
f. Reduce 

Hy 

g.  Unit is under defrost mode 
h.  Unit is under anti-short cycle delay  
i. 

Call service for diagnosis 

2. Unit not 

starting , but 
temperature 
rising high  

a.  Anti-short cycle  
 

a. Reset AC 
 

3. Temperature 

fluctuating 

a. Air probe 
 

a.  When using an air probe, the wine 

bottle temperature is mainly 
controlled by the average air 
temperature. If the set-point is 55

°

with the differential 4F, the cooling 
unit turns on at 59

°

F of air 

temperature (It may be higher than 
59

°

F if it is in anti-short cycle or 

defrost cycle) and turns off at 55

°

of air temperature. The average air 
temperature is 57

°

F, and then the 

wine temperature is around 57+/-
0.5

°

F. The air is light enough to 

change so quickly that it maintains 
relatively constant average 
temperature that would prevent wine 
bottle temperature from fluctuating. 

4. Temperature  

high, unit 
stopping 
and starting 
normally 

a. Temperature 

setting 

high 

 

a. Lower 

the 

setting 

 

5. Temperature  

high, unit 
stopping 
and starting 
with short 
running time 

a. 

Air probe touching the 
evaporator coil, displaying 
temperature ok 

b. Air probe in cold-air supply, 

displaying temperature ok  

c.  Failed controller and probe 

a.  Move the air probe away from the 

evaporator 

 
b.  Move the air probe away from the 

cold-air supply 

c.  Call service for diagnosis 

6. Temperature 

a.  Improper cellar insulation & seal 
 

a.  Check insulation, gasket and door 

opening 

Summary of Contents for Wine-Mate WM-2500SSDWC

Page 1: ...iling Split Cooling System Installation Operation Care Manual WM 2500SSDWC WM 4500SSDWC WM 6500SSDWC WM 8500SSDWC w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th...

Page 2: ...1 Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 20 AMP circuit for WM 2500SSDWC and 30 AMP for WM 4500 8500SSDWC are required...

Page 3: ...le of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 25 Customer Support 27 Warran...

Page 4: ...erature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer...

Page 5: ...ellars 50 ft so that noise and compressor vibration are isolated SSDWC condensing units are water cooled so that exhaust ventilation is not needed SSDWC evaporator units provide two way air supply ope...

Page 6: ...SCU WC 24x18x18 2500 350 250 R134a 115V 60HZ 1A 115V 60HZ 5 7A 20 40 WM 4500SSDWC WM 45SFCD 23x17 5x10 5 WM 450SCU WC 24x18x18 4500 460 1000 R134a 115V 60HZ 1A 115V 60HZ 6 9A 25 60 WM 6500SSDWC WM 65S...

Page 7: ...o lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock t...

Page 8: ...etting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setti...

Page 9: ...lar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 9 How to set low cellar temper...

Page 10: ...elay min 1 ot probe calibration 0 US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative...

Page 11: ...aning To clear any sediment that may accumulate the water regulating valve may be manually flushed Insert screwdrivers under both sides of the valve spring guide and lift upwards to flush 2 Condensate...

Page 12: ...temperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it...

Page 13: ...r suction pressure too high a Check compressor windings start relay and overload protector b Check water flow c Call service for removing refrigerant d Call service for information 9 Evaporator fan ru...

Page 14: ...Call service 13 Noisy operation a Mounting area not firm b Loose parts c Compressor overloaded due to improper condenser cooling d Defective components a Add support to improve installation b Check fa...

Page 15: ...s The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the distance between th...

Page 16: ...15 CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 25 45SFCD Evaporator Unit...

Page 17: ...16 Fig 4 WM 65 85SFCD Evaporator Unit...

Page 18: ...17 Fig 5 WM 250 850SCU WC Condensing Unit Fig 6 Liquid Filter Fig 7 Liquid Indicator...

Page 19: ...on pump must be used 3 Condensing Unit Installation 1 Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun The location shall be adequately ventilated and shall not...

Page 20: ...out Connection Water Pressure Drop PSI WM 2500SSDWC WM 250SCU WC 0 2 3 8 FPT 1 2 ODF SOLDER 0 2 WM 4500SSDWC WM 450SCU WC 0 4 3 8 FPT 1 2 ODF SOLDER 0 2 WM 6500SSDWC WM 650SCU WC 0 6 3 8 FPT 1 2 ODF S...

Page 21: ...ondensing unit is installed above the evaporator unit use the suction line one listed size smaller Expansion and solenoid valves have been installed on the liquid line 1 The installation order starts...

Page 22: ...tate and local codes 8 Evacuating Charging and Starting the system CAUTION Always use the superheat and subcooling pressure readings to charge refrigerant properly the listed charge amounts are used f...

Page 23: ...F wine cellar temperature 6 Again you must verify if the superheat at the evaporator unit is around 9 18 F at 55 F wine cellar temperature under high low water temperatures 7 If the superheat is high...

Page 24: ...ing s Low suction pressure and low head pressure Low superheat and low subcooling t Low suction pressure and low to normal head pressure High superheat and normal to high subcooling u Low suction pres...

Page 25: ...components 4 Low pressure control shutting down the system 5 High pressure control shutting down the system 1 Check for proper voltage 2 Check all wirings and connections 3 Check start relay start cap...

Page 26: ...rical Wiring Diagrams CAUTION Hidden lines are the field wirings Use minimum 14 gauge wires for power lines A safety switch is always recommended for the condensing unit Fig 14 WM 2500 4500SSDWC Wirin...

Page 27: ...26 Fig 15 WM 6500 8500SSDWC Electrical Wiring Diagram...

Page 28: ...7 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp co...

Page 29: ...ties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products...

Page 30: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...

Reviews: