background image

                                                       

 

                       

 

- 27 - 

Electrical Wiring Diagrams 

 

CAUTION 

Hidden lines are the field wirings 
Use minimum 14 gauge wires for power lines. 
If  equipped  with  low  ambient  condition  kit,  use  low  ambient 
temperature wiring diagrams. 
A safety switch is always recommended for the condensing unit.

 

 

 

 

Fig. 16 WM-1500~4500SSL Electrical Wiring Diagram 

 

Summary of Contents for WINE-MATE WM-1500SSL

Page 1: ...SL LA WM 4500SSL WM 4500SSL LA WM 6500SSL WM 6500SSL LA WM 8500SSL WM 8500SSL LA www vinotem www vinotemp com p com Read and save these instructions Read and save these instructions Vinotemp Internati...

Page 2: ...1 Important Safety Information...

Page 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 27 Warranty 30...

Page 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by more than 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a tim...

Page 5: ...m storage of wine like that in natural caves SSL evaporator units can be installed on the ceiling in a small cabinet or room The evaporator units provide low profile and whisper quiet operation SSL co...

Page 6: ...ent temperatures or lower insulations will cause reducing capacity and the cellar temperature may not be maintained at 55 F The specifications are listed as follows Model No Capacity Btu h Airflow CFM...

Page 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Page 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Page 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Page 10: ...ative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the se...

Page 11: ...ng Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Remo...

Page 12: ...oling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F and then...

Page 13: ...rt capacitor overload protector compressor c Call service 9 Compressor running but condenser fan not running a Fan blade stuck b Incorrect or loose wirings c Failed motors d Fan cycle control a Check...

Page 14: ...cessive condensate b High humidity causing excessive condensate c Drain restricted a Check for any air leak b Use drain line c Clean the drip tray and drain line 17 Condensate inside ducts a Drain lin...

Page 15: ...Installation of the system must be done in accordance with all state and local building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suc...

Page 16: ...4 5 x 4 75 29 75 x 14 75 WM 250SCUR 18 x 14 x 12 115V 60HZ 1A 115V 60HZ 5A 20A 29 40 WM 2500SSL LA WM 25SFCL 31 75 x 14 5 x 4 75 29 75 x 14 75 WM 250SCUR LA 18 x 14 x 12 115V 60HZ 1A 115V 60HZ 6A 20A...

Page 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 15 25SFCL Evaporator Unit...

Page 18: ...17 Fig 5 WM 45 85SFCL Evaporator Unit Fig 6 WM 150 450SCUR Condensing Unit...

Page 19: ...d in the wine cellar 5 ft above the floor or the air return area but it shall not be located in the air supply area or other areas where air is not circulated 3 Air probe can be pulled out of the temp...

Page 20: ...ntilated location Otherwise heat exhausted by the condensing unit will build up and the cooling system will not operate properly 2 Condensing unit shall be elevated to avoid possible flooding and shad...

Page 21: ...long use both inverted U trap and suction accumulator to prevent liquid from flooding back to the compressor 3 If the condensing unit is located below the evaporator unit use inverted U trap to preve...

Page 22: ...the superheat subcooling and pressure readings to charge refrigerant properly If the unit is equipped with a low ambient condition kit and installed in the summer add 15 more refrigerant If the low am...

Page 23: ...ting and Completing the Installation 1 Checking pressure control settings I The encapsulated pressure control if applicable Suction pressure setting fixed Cut in 32 psig Cut out 10 psig Fig 12 Fixed P...

Page 24: ...e compressor and shall be turned on all the time The heater is self regulated B The condenser fan control The condenser fan control is installed at the high side It closes on rise of pressure It is ne...

Page 25: ...first to see if the refrigerant charge is sufficient If the charge is not sufficient add more refrigerant Liquid must always be charged into the hide side when the compressor runs If the charge is go...

Page 26: ...High superheat and normal to high subcooling 12 Low suction pressure and normal head pressure High superheat and normal subcooling 13 Low suction pressure and high head pressure High superheat and hi...

Page 27: ...d components 4 Low pressure switch shutting down the system 5 high pressure switch shutting down the system 1 Check for proper voltage 2 Check all wirings and connections 3 Check start relay start cap...

Page 28: ...he field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condens...

Page 29: ...28 Fig 17 WM 1500 4500SSL LA Electrical Wiring Diagram Fig 18 WM 6500 8500SSL Electrical Wiring Diagram...

Page 30: ...29 Fig 19 WM 6500 8500SSL LA Electrical Wiring Diagram...

Page 31: ...and is in lieu of all other warranties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any...

Page 32: ...NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to properly...

Reviews: