-22-
Fig. 10 Fixed Pressure Control
II.
The adjustable
pressure control (if applicable for pump-down)
Suction pressure setting: Cut out=5 psig; Cut in=25 psig; Differential=20 psig
Head pressure setting: Cut out=230 psig; Cut in=150 psig; Differential=80 psig
It is necessary to adjust the setting in the field to reach the correct cycle time.
A. P70 Single/Dual Control
B. PS2 Dual Control
Fig. 11 Adjustable Pressure Control