Vinotemp WIME-MATE WM-1500SSI Operation Care Installation Manual Download Page 9

                                                       

 

                       

 

- 8 - 

5. Manual Defrost 

 
Press and hold the defrost 

 key until defrost starts. The defrost indicator will be 

on.  
 

6. Parameter Programming 
 

1) Press and hold the 

SET 

+  keys until the “

°C”  or  “°F” 

LED starts flashing, 

then release the keys. 
2) Press and hold again the

  SET 

+  keys until the 

Pr2 

label is displayed, then 

release the keys. The first parameter 

Hy

 will be displayed. 

3) Press up/down keys

/  to scroll to the required parameter within 10 sec. 

4) Press the “

SET

” key to display its value. 

5) Use up/down keys

 to change its value within 10 sec. 

6) Press “

SET

” to store the new value and the display will flash 3 times. 

7)

 To exit

: Press 

SET + 

 or wait 15sec without pressing a key. 

 

PARAMETER 

DESCRIPTION 

DEFAULT VALUE 

Set 

set-point (

°

55 

Hy 

temperature regulation differential 

(

°

AC 

anti-short cycle delay (min)

 

10 (hidden) 

Con 

compress on with probe faulty (min) 

15 

CoF 

compress off  with probe faulty (min) 

30 

CF 

temperature unit 

(

°

F

/ °

C

)

 

F: Fahrenheit 

rES 

display resolution 

in: integer 

dLy 

temperature display delay (min) 

ot 

probe calibration 

(

°

)

 

LS 

minimum  set-point 

(

°

)

 

50 

US 

maximum set-point 

(

°

)

 

65 

idF 

defrost interval time (hour)

 

12 

MdF 

defrost endurance time (min)

 

30 

ALC 

temperature alarm type

 

rE: relative to set-point 

ALU 

high temperature alarm 

(

°

10 

ALL 

low temperature alarm 

(

°

10 

AFH 

alarm recovery differential 

(

°

)

 

ALd 

temperature alarm delay (min) 

60 

dAO

 

temperature alarm delay on startup (hr)   

23 

SAA 

heater set-point 

(

°

)

 

40 

SHy 

heater regulation differential 

(

°

)

 

FSU 

fan action 

Std 

FnC 

fan operating mode 

C-n: on with compressor & off during defrost 

Fon 

fan on with compressor off (min)

 

FoF 

fan off with compressor off (min) 

15 

 

NOTE 

Depending on the controller, not all parameters are available

 

Summary of Contents for WIME-MATE WM-1500SSI

Page 1: ...0SSI LA WM 2500SSI WM 2500SSI LA WM 4500SSI WM 4500SSI LA www vinotemp com www vinotemp com Read and save these instructions Read and save these instructions Vinotemp International Corp 17631 S Susana...

Page 2: ...1 Important Safety Information...

Page 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 25 Warranty 27...

Page 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by more than 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a tim...

Page 5: ...storage of wine like that in natural caves SSI evaporator units can be recessed and flushed in the ceiling in a wine room The evaporator units provide 6 low profile and whisper quiet operation SSI co...

Page 6: ...nd R19 exterior insulations Higher ambient temperatures or lower insulations will cause reducing capacity and the cellar temperature may not be maintained at 55 F The specifications are listed as foll...

Page 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Page 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Page 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Page 10: ...ative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the se...

Page 11: ...ng Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Remo...

Page 12: ...oling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F and then...

Page 13: ...rt capacitor overload protector compressor c Call service 9 Compressor running but condenser fan not running a Fan blade stuck b Incorrect or loose wirings c Failed motors d Fan cycle control a Check...

Page 14: ...cessive condensate b High humidity causing excessive condensate c Drain restricted a Check for any air leak b Use drain line c Clean the drip tray and drain line 17 Condensate inside ducts a Drain lin...

Page 15: ...Installation of the system must be done in accordance with all state and local building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suc...

Page 16: ...5SFCI 48 3 16 x 12 3 16 x 6 3 8 2 1 2 WM 150SCUR 18 x 14 x 12 115V 60HZ 1A 115V 60HZ 4A 20 27 30 WM 1500SSI LA WM 15SFCI 48 3 16 x 12 3 16 x 6 3 8 2 1 2 WM 150SCUR LA 18 x 14 x 12 115V 60HZ 1A 115V 60...

Page 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 15 45SFCI Evaporator Unit...

Page 18: ...ated in the wine cellar 5 ft above the floor or the air return area but it shall not be located in the air supply area or other areas where air is not circulated 3 Air probe can be pulled out of the t...

Page 19: ...flooding and shaded from direct sun It shall not be exposed to temperatures higher than 110 F or lower than 50 F 3 Leave minimum 5 ft clearance for the air exhaust side and leave minimum 1 foot clear...

Page 20: ...erted U trap to prevent liquid from flooding back to the compressor If the elevation difference is more than 10 ft use both inverted U trap and suction accumulator 4 If the condensing unit is located...

Page 21: ...e compressor after the condensing unit has been powered for 12 hours 1 Turn both discharge and suction valves in the middle positions 2 Connect the manifold high or low pressure hose to the discharge...

Page 22: ...ressure setting Cut out 5 psig Cut in 25 psig Differential 20 psig Head pressure setting Cut out 230 psig Cut in 150 psig Differential 80 psig It is necessary to adjust the setting in the field to rea...

Page 23: ...liquid indicator 3 The head pressure shall be 120 150 psig at 70 90 F condensing unit operating temperatures 4 The evaporator s constant pressure expansion valve is set around 30 35 psig 35 40 F at f...

Page 24: ...2 High suction pressure and low head pressure Low superheat and low subcooling 3 High suction pressure and high head pressure Low superheat and high subcooling 4 High to normal suction pressure and hi...

Page 25: ...e and high head pressure Normal to high superheat and high subcooling 8 Liquid line restricted after receiver solenoid valve restricted 9 Suction line restricted 10 Air restricted at evaporator evapor...

Page 26: ...he field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condens...

Page 27: ...26 Fig 15 WM 1500 4500SSI LA Electrical Wiring Diagram...

Page 28: ...and is in lieu of all other warranties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any...

Page 29: ...NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to properly...

Reviews: