Page 8

shading solutions by

VIMCO

TM

A

C

1 2 3 4

5 6 7 8

Cntrl 1

Cntrl 2

G

rou
nd

AC

AC

Com

MUX

MUX

B

Do not connect if there is only one MDU in the system

. If

there are multiple MDU's in the  system, the MDU's must be wired
together. Connect the MUX, Drain, and MUX terminals of each MDU
together in a daisy chain or homerun configuration.

To a 

Sivoia

®

wall mounted keypad, or a 

Sivoia

®

interface such

as the SV-CCI-GRP or the SV-GRXI. The CNTRL1 and CNTRL2
wires are polarity sensitive.

MDU WIRING - SINGLE MOTOR

Connecting Wires to the MDU Terminal Block

The terminal block located at the bottom of the MDU is the wire
connection point for: power, communication, keypads, and interfaces.

A.

Remove terminal block cover (if not yet removed) by pressing in on
the cover and then pulling downward.

B.

Grasp terminal block and pull down to separate from connecting
block.

C.

Connect wires to the terminal block according to the diagram
below.

D.

Replace the terminal block and the terminal block cover.

Wire to a 

Sivoia

®

plug-in transformer, junction box mount

transformer, or a 

Sivoia

®

power panel. Each MDU must be EARTH

grounded. One 

Sivoia

®

transformer can power 

ONLY ONE MDU

regardless of shade size.

A

B

Control

Comm

Link

Power

Supply

Comm & Power

(         &          combined)

Wire Type

Control

Description

2 conductors / #22-24 AWG

3 conductors (2 shielded, 1 common) / #24 AWG
Belden

®

wire model #1883A

3 conductors #22 AWG

Lutron

model # SV-IR-EXT-10

3 conductors:

2 / #18-22 AWG (24 VAC power supply)
1 / #18-22 AWG (earth ground)

6 conductors:

2 / #16 AWG (24 VAC power supply)
1 / #18 AWG (earth ground)
3 #22 AWG sh 1 #24 AWG common (comm link)

(Lutron wire model no. SV-CBL-MDU-250)

Control to MDU: 250 ft. (76 m)

Max. Length

4000 ft. (1333 m) per system
1000 ft. (333 m) from MDU to MDU

50 ft. (15 m) per system - total of 5
SV-IR-EXT-10, 10 ft. (3 m) each

MDU to 

Sivoia

®

power panel:

200 ft. (61 m)

Transformer to MDU:

#18 AWG - 150 ft. (46 m)
#20 AWG - 100 ft. (31 m)
#22 AWG - 60 ft. (18 m)

A

Comm Link

B

B

D

Power Wires

C

C

SV-IR Extension 
Cable

E

5

Summary of Contents for Lutron Sivoia

Page 1: ...13 9 Troubleshooting pg 14 10 Part Specs pg 15 Contents Infrared Handheld Transmitter Idler Support Fabric Roller Assembly Motor Drive Unit MDU Wallstation Controls Transformer SV IR Infrared Receiver...

Page 2: ...separately MDU Idler Support Mounting Brackets MDU Idler Support Ceiling Mount Brackets Idler Support 1 2 Idler and MDU Truss head Screws x8 2 Pan Head Mounting Bracket Screws x8 2 Phillips Screwdrive...

Page 3: ...Sivoia Order Invoice to accurately position the mounting brackets Bracket to Bracket Width FW 4 102 mm Fabric Width FW 2 3 4 70 mm 1 1 4 32 mm Bracket to Bracket Width FW 4 102 mm Fabric Width FW 2 3...

Page 4: ...ets to studs in the wall using no less than four 4 pan head mounting bracket screws Note All four 4 screws must be securely fastened to stud or other structural member Fabric Width 5 127mm 5 127mm A B...

Page 5: ...must be securely fastened to stud or other structural member Fabric Edge Wall Ceiling Bracket Top View 5 127mm Line up this bracket edge with the fabric edge Face this opening outward towards the roo...

Page 6: ...three 3 truss head screws HANGING THE SHADE A Unwrap approximately 1 ft 0 3 m of material B Attach the shade to the MDU first by engaging the roller s hexagonal socket with the motor s hexagonal driv...

Page 7: ...eep the idler pin secure locked E Adjust the shade leveling screw to level the shade roller D D E E Shade Retaining Screw Locked Shade Retaining Screw Shade Leveling Screw CAUTION Not setting the shad...

Page 8: ...he terminal block according to the diagram below D Replace the terminal block and the terminal block cover Wire to a Sivoia plug in transformer junction box mount transformer or a Sivoia power panel E...

Page 9: ...Terminal Blocks Control Comm Link Comm Link Power Supply Control Next MDU Next MDU Comm Link Power Supply Wire Type Control Description 2 conductors 22 24 AWG 3 conductors 2 shielded 1 common 24 AWG...

Page 10: ...position desired Use the Open and Close buttons on the MDU to adjust the shade to the closed position desired Press the Set button to save the corrent position as the Open Limit The display will read...

Page 11: ...terfaces and individual keypads interfaces can be wired to the same MDU A maximum of 9 keypads interfaces can be wired to one MDU There are two types of Sivoia keypads and interfaces group and individ...

Page 12: ...4 seconds until appears in the MDU s LED display OPEN PRESET CLOSE PRESS ONCE Shade goes to open limit PRESS ONCE Shade goes to close limit PRESS To lower shade PRESS To raise shade PRESS ONCE Shade...

Page 13: ...ive 5 SV IR EXT 10 extension cables 10 ft 3 m each Note To control an individual shade with an IR transmitter the SV IR must be connected to that MDU If there is a Group Subgroup of MDU s with the sam...

Page 14: ...on the roller frame or end brackets Check for and clear all obstructions The shade does not respond to control 1 Check that power is connected to the shade 2 Check that the wall keypad has been wired...

Page 15: ...mm 3 91 99 mm 3 91 99 mm 2 84 72 mm 2 20 56 mm 3 20 81 mm 0 5 13 mm Idler Support MDU Mounting Bracket Idler Mounting Bracket Ceiling Mount Bracket MDU Dimensions Side View A Side View B Front View Fr...

Page 16: ...d equipment external to the SIVOIA Motorized Window Shade System such as a Non Lutron lighting and automation systems b Building wiring and c Other manufacturers equipment including but not limited to...

Reviews: