Vimar 01504.2 Installer Manual Download Page 10

   10

ETS-Parameters line coupler - Application description line repeater

7. Application description line repeater

Line repeaters do not use a filter table. A received telegram is routed to all lines irrespective of in which line it is processed. It is therefore not important whether the 
telegram is triggered within a line or whether it is sent from an upper line to a lower line via a coupler.
When an error occurs during transmission of a telegram according to the physical address of a receiver the line repeater is able to repeat the telegram. With the param-
eters „Physical:
Repetition if errors on main line/on sub line“ this function can be set separately for both lines.
In case of routing a group telegram with not receiving an acknowledgement or in case of a bus device detecting a transmission error the line repeater repeats the 
telegram three times.
With the parameters „Group: Repetition if errors on main line/on sub line“ this function can be adjusted separately for both lines.

ETS-Text

Selection

[Factory default]

Comment

Configuration

groups: filter, physical: block groups, physical: filter
groups: route, physical: filter groups, physical: route 
configure

[groups, physical: filter]

Block

: no telegram is routed.

Filter

: only telegrams are routed which are entered in the filter table.

Route

: the telegrams are routed.

Configure: the following parameters can be set manually.

Group telegrams

1. transmit all 

(not recommended)

2. block
3. filter

[filter]

1. All group telegrams are transmitted.
2. No group telegram is transmitted.
3. Only group telegrams entered in the filter table are routed.
ETS3/4 produces the filter table automatically

Sub group
telegrams 14/15

1. transmit all
2. block 

[transmit all]

1. Group telegrams with the sub group 14 or 15 (e.g. 14/1) are routed.
2. Group telegrams with the sub group 14 or 15 (e.g. 14/1) are not routed.

Physical telegrams

1. transmit all 

(not recommended)

2. block
3. filter

[filter]

1. All Physical telegrams are transmitted.
2. No Physical telegram is transmitted.
3. Depending on the physical address only Physical telegrams are routed.

Physical: Repetition
if errors on the sub
line occur

1. no
2. normal
3. reduced

[normal]

If a transmission error (e.g. due to missing receiver) is found after sending a 
physical telegram on the main line:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once.

Group: Repetition if
errors on the sub
line occur

1. no
2. normal
3. reduced

[normal]

If a transmission error (e.g. due to missing receiver) is found after sending a 
group telegram on the main line:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once..

Telegram
confirmations on line

1. if routed 
2. always

[if routed]

1.  Only telegrams which are to be routed are confirmed on the sub line 

(ACK).

2. Each telegram on the sub line is confirmed (ACK).

Send confirmation
on own telegrams

1. yes 
2. no

[no]

1.  Every telegram on the sub line is confirmed with its own ACK (from the 

Line coupler).

2. No confirmation with own ACK

Summary of Contents for 01504.2

Page 1: ...Installer manual BUILDING AUTOMATION 01504 2 Line Field coupler KNX standard...

Page 2: ...Contents...

Page 3: ...ode 6 4 3 Function button 6 4 3 1 Manual function 6 4 3 2 Factory reset 6 5 Application description line coupler 7 6 ETS Parameters line coupler 7 6 1 Settings 7 6 2 General 8 6 3 Main line 8 6 4 Sub...

Page 4: ...ally addressed telegrams in this document named Physical telegrams or according to the built in filter tables for group oriented communication Group telegrams Compared to other similar products the 01...

Page 5: ...dress filtering status LED 7 Programming LED A Function button B Program button C KNX main line D KNX sub line 3 1 Installation example 01501 2 POWER SUPPLY UNIT L N AUX KNX 30V KNX 120 240V 50 60Hz 3...

Page 6: ...e With the Programming button the device can be switched between Normal Mode and Program Mode To download the physical address to the device this function is essential After the download the 01504 2 a...

Page 7: ...er that is set by ETS With the parameters Repetitions if errors this function can be adjusted separately for both con nected lines The default settings of these parameters should be retained 6 ETS Par...

Page 8: ...f automatically Manual function disabled pass all telegrams pass physical telegrams pass group telegrams pass all telegrams Telegram routing configuration for the Manual Function Fig 5 General Fig 6 M...

Page 9: ...3 Depending on the physical address only Physical telegrams are routed Physical Repetition when errors on main line 1 no 2 normal 3 reduced normal If a transmission error e g due to missing receiver i...

Page 10: ...filter 1 All group telegrams are transmitted 2 No group telegram is transmitted 3 Only group telegrams entered in the filter table are routed ETS3 4 produces the filter table automatically Sub group t...

Page 11: ...Line repeater has to be downloaded to the device Under the Information tab this configuration can be changed by the menu Change Application Program After changing the configuration the filter table e...

Page 12: ...ams will be repeated only once Group Repetition when errors on main line 1 no 2 normal 3 reduced reduced If a transmission error e g due to missing receiver is found after sending a Group telegram on...

Page 13: ...d up to three times 3 Physical telegrams will be repeated only once Group Repetition if errors on the sub line occur 1 no 2 normal 3 reduced reduced If a transmission error e g due to missing receiver...

Page 14: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com 01504 2 EN 03 2102...

Reviews: