NT00000534-KSCR-ECOWATT-08-18-28-38-52-AN-200625
21/76
ENGLISH
In d i c a t i o n s
Operation:
The green LED is lit when the CORRIGO is energised with voltage.
Alarm:
The red LED flashes and the alarm text is displayed on the screen.
General alarm: This output can be configured.
E tool© configuration software
Equipment required: operating system MS Windows 2000, 8, 7, XP, Vista, Windows 7, Windows 8 or
Windows 10 available on www.vim.fr.
6 . 2 A HU p o w e r c o n n e c t i o n w i t h e l e c t r i c a l h e a t e r
A separate and protected power supply is to be provided for each unit.
The electrical cabinet is dedicated for command and power wirings.
Dampers are to be provided as accessories. Damper actuators are connected to the KSCR control 24 V
power supply.
Dampers are to be provided for the accessories. The damper servomotors are powered by the power sup
-
ply to the KSCR control at 24 V.
K SC R EC O W A T T
®
0 8 - 1 8 - 2 8 - 3 8
M
AHU power supply
Accessory :
damper driving
Accessory :
damper driving
Fresh air
Supply air
M
M o d e l EI
On the EI models, an electrical heater is installed inside the unit. It is fully wired and connected to the
control. There is only one power supply except for the KSCR 52 with 48kW electrical heater, which has
a separate power supply for its electrical heater. Thermostat locations and manual thermostat resetting:
R e s e t b u t t o n f o r K SC R EC O W A T T
®
0 8 - 1 8 - 2 8 - 3 8
Automatic thermostat
Manual thermostat
The electrical heater includes the manual and automatic security
thermostats and its autonomous static command controller.
3 lamps «Control», «Load», and «Alarm» reflect their status :
- 1 : light «Control» green : SSR turned on (waiting for command).
- 2 : light «Load» orange : Command 0-10V active.
- 3 : light «Alarm» red : SSR fault.
1
2
3
Control
Load
Alarm