background image

TECHNICAL DATA

ESFR UPRIGHT SPRINKLER 

SIN VK520 (K14.0)

Page 3 of 5

Form No. F_060298   19.11.15    Rev 19.2

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

G. System design must be based on ESFR design guidelines described in applicable FM Global Loss Prevention Data Sheets, 

the National Fire Protection Association, and the Authorities Having Jurisdiction. 

NOTE: Viking recommends installing one 

style  of  sprinklers  (either  pendent  or  upright)  throughout  ESFR  systems.  However,  provided  the  fusible  elements 

are installed within the distance below the ceiling allowed by the installation standards, and when acceptable to the 

Authority Having Jurisdiction, Viking considers the practice of mixing upright and pendent ESFR sprinklers to be ac

-

ceptable.

 

5.  OPERATION

During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the seat and spring assemblies to open 

the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to suppress 

the fire.

6.  INSPECTIONS, TESTS AND MAINTENANCE

A. The sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency 

of inspections may vary due to corrosive atmosphere, water supplies, and activity around the device.

B. Sprinklers that have been painted or mechanically damaged must be replaced immediately. Sprinklers showing signs of cor-

rosion shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if 

necessary, replaced after a specified term of service. For Viking ESFR Upright Sprinklers, refer to the Installation Standards (e.g., 

NFPA 25) and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. 

Sprinklers that have operated cannot be reassembled or reused, but must be replaced. When replacing sprinklers, use only 

new sprinklers.

C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or 

otherwise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers 

installed.

D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/

or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should 

be given to employment of a fire patrol in the affected area.

1. Remove the system from service, drain all water, and relieve all pressure on the piping.

2. Using the special sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that the 

replacement sprinkler is the proper model and style, with the correct orifice size, temperature rating, and response charac-

teristics. A fully stocked spare sprinkler cabinet should be provided for this purpose.

3. Place the system back in service and secure all valves. Check the replaced sprinklers and repair all leaks.

E. Sprinkler systems that have been subject to a fire must be returned to service as soon as possible. The entire system must 

be inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of 

combustion, but have not operated, should be replaced. Refer to the Authorities Having Jurisdiction for minimum replacement 

requirements.

7.  AVAILABILITY

The Viking Model VK520 Sprinkler is available through a network of domestic and international distributors. See The Viking 

Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

NOTICE

The  owner  is  responsible  for  maintaining  the  fire  protection  system  and  devices  in  proper  operating  condition.  For 

minimum maintenance and inspection requirements, refer to the NFPA standard that describes care and maintenance 

of sprinkler systems. In addition, the Authorities Having Jurisdiction may have additional maintenance, testing, and 

inspection requirements that must be followed.

Summary of Contents for VK520

Page 1: ...rubber tire stor age may be protected by Viking ESFR Upright Sprinkler VK520 2 LISTINGS AND APPROVALS FM Approved Class 2008 NYC Approved MEA 89 92 E Volume 18 China Approval Approved according to China GB Standard Refer the Approval Chart and Commodity Selection and Design Criteria Overview for FM Approval requirements that must be followed 3 TECHNICAL DATA Specifications Minimum Operating Pressu...

Page 2: ...ler wrench 05118CW B shown in Figure 1 for installing ESFR Sprinkler VK520 With the sprinkler contained in the protective cap install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler wrench flats only while taking care not to damage the sprinkler operating parts DO NOT use any other type of wrench as this could damage the unit DO NOT use the sprinkler deflector or fu...

Page 3: ... must be replaced When replacing sprinklers use only new sprinklers C The sprinkler discharge pattern is critical for proper fire protection Therefore nothing should be hung from attached to or otherwise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from ser...

Page 4: ...emperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirement...

Page 5: ... to Bulletin Form No F_091699 Care and Handling of Sprinklers Viking ESFR Pendent Sprinklers are to be installed in accordance with the latest edition of Viking technical data the latest standards of FM Global VdS LPCB and any other Authorities Having Jurisdiction and also with provisions of governmental codes ordinances and standards whenever applicable Approval Chart ESFR Upright Sprinkler VK520...

Reviews: