QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK4611 (K2.8)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 7 of 8
Form No. F_061620 21.10.07 Rev 21.2
Replaces Form No. F_061620 Rev 20.4
(added hole cut dimensions)
C
E
D
D
Figure 6: Using the Sprinkler Wrench
Step 1:
Insert the wrench (A) into the slots (B) on the
protective cap (C).
B
A
USE ONLY the designated sprinkler wrenches shown in this document. Permanent damage to the
sprinkler assembly can occur if the proper wrench is not used. Other sprinkler wrenches available from
Viking may fit into the sprinkler adapter cup; however, only the wrenches shown here are designed to
properly install this sprinkler.
Step 2:
Rotate the wrench slightly in either direction
until the tines on the wrench (D) line up with
the vent openings (E) on the adapter cup and
lock into place. NOTE: A leak tight seal must
be achieved. Turn the sprinkler clockwise
1 to 1-1/2 turns past finger-tight.
A
C
B
Figure 7: Using the Cap Removal Tool
Step 1:
Attach a piece of CPVC pipe as shown
and tighten the thumb screw (not
shown); then, insert the tool (A) into
the slots (B) in the protective cap (C).
Step 2:
Rotate the tool slightly to lock into
place.
Step 2:
Gently, pull downward to remove
the protective cap. The deflector will
slide downwards on the pins.