1.  INTRODUCTION

The purpose of this bulletin is to inform users of proper XG Guard usage for the  Model XT1 Sprinklers. The XG Guard assemblies 

are specifically listed and approved for use on Model XT1 Sprinklers; no other guard assemblies should be used. 

 

 

WARNING  

Viking sprinklers are manufactured and tested to meet the rigid requirements of the approving agency. The sprinklers 

are designed to be installed in accordance with recognized installation standards. Deviation from the standards or 

any alteration to the sprinkler after it leaves the factory including, but not limited to: unlisted accessories, painting, 

plating, coating, or modification, may render the sprinkler inoperative and will automatically nullify the approval and any 

guarantee made by The Viking Corporation. Refer to the Authority Having Jurisdiction prior to installation.  

2.  GENERAL INFORMATION: 

A potential product performance issue may exist when listed products are combined with unlisted product(s) that have not been 

evaluated together by a recognized approval laboratory. With the development of new products and existing products, it is extremely 

important to correctly match a sprinkler with a sprinkler guard. Please refer to the appropriate manufacturer’s technical literature or 

call Viking Technical Services at 877-384-5464.

  

IMPORTANT

 

Model XT1 sprinklers are specifically listed and approved with XG Guard. The XG Guard, part number 22931, is listed 

and approved for use with the following XT1 sprinklers: VK1001, VK1021, VK3001, VK3021, VK2002, VK2022, VK3502, 

VK3522, VK2001, VK2021, VK3501, VK3521.

Refer to the Guards and Water Shields for XT1 Sprinklers Technical Data Sheet at the following link:  

https://www.vikinggroupinc.com/sites/default/files/documents/021319.pdf

 

Listed and Approved XG Guard/XT1 Sprinkler Assembly

Unlisted Guard/XT1 Sprinkler Assembly

Activation 

element T-hinge 

blocked

Summary of Contents for VK1202

Page 1: ...PT Nominal K factor 8 0 U S 115 metric Glass bulb fluid temperature rated to 65 F 55 C Metric K factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 Material Standards Sprinkler Body Brass CW602N UNS C84400 or QM Brass Deflector Stainless Steel UNS S30400 Pip Cap Shell Stainless Steel UNS S44400 Pip Cap Disc Stainles...

Page 2: ...erature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler Accessories Sprinkler Wrenches see Figure 1 A Installer Wrench Part No 22055 B Cabinet Wrench Part No 20901M B C Straight Wrench Part No 22940MB Sprinkler Cabinet A Up to 6 sprinklers Part number 01724A B 6 12 Sprinklers Part number 01725A Footn...

Page 3: ...NFPA LPCB or other similar organizations and also with the provisions of governmental codes ordinances and standards whenever applicable Figure 3 Installation Frame arms parallel to the pipe 1 2 3 1 Slide the wrench around the protective cap 2 Press the wrench downward to engage on the wrench flats 3 Rotate the wrench clockwise to install the sprinkler NOTE The sprinkler frame arms shall be parall...

Page 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 8: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Page 9: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Page 10: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Page 11: ...he sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may affe...

Page 12: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Page 13: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Page 14: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Page 15: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Page 16: ...y render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERAL INFORMATION A potential product performance issue may exist when listed products are combined with unlisted product s that have not been evaluated together by a recognized approval laboratory With ...

Reviews: