Viking VBCV3638 Installation Manual Download Page 10

10

WALL INSTALLATION 
EXTERIOR-POWER VENTILATOR

DEV900-Exterior-Power Ventilator Kit (900CFM)

1.  Choose a position on the outside wall.  Min. 24” (61.0

cm from ground may vary depending on local codes
or location.  Make sure that no wall studs, pipes or
wires run through the opening area.

2.  Drill a guide hole at the center of the opening area.
3.  From the outside, use the guide hole as a starting

point to lay out the installation.

A.  Use a T-square to measure 10

3/4

” (27.3 cm) to the

left of the guide hole, then 12

7/8

” (32.7 cm) to

locate the top-left corner of the layout.

B.  Starting from the top -left corner,  mark a 25”

(63.5 cm) by 28

1/2

” (72.4 cm) rectangle on wall

located from guide hole.

4.  Cut a rectangular hole in the siding only.  Do not cut

the sheathing. Nail down all siding ends.

5.  Mark an 11” (27.9 cm) diameter circle centered on the

guide hole and mark the center of the 1

1/4

” diameter

electrical wiring hole.

6.  Cut the 11” (27.9 cm) hole in the sheathing and drill

the 1

1/4

”(3.2 cm) as marked.

7.  Place a large bead of caulk on the back side of the

housing along the outer edge.

8.  Center the blower ring in the 11” (27.9 cm) diameter

hole, making sure that the 1

1/4

” (3.2 cm) diameter

electrical wiring hole aligns with the hole in the wiring
box. 

9.  Attach blower to the wall with the six screws

provided.  It is recommended that the screws
be located inside the blower housing.  All six
holes in the back panel must be filled, or any
moisture that may get inside the housing could
leak into the house.

10.  Using a good grade of caulk, seal all around the

mounting screw heads.

11.  Bring electrical wiring through the hole in the

wiring box and secure it according to local
codes.

12.  Make the electrical connections with the proper

connector for the type of wire being used.
Connect white to white, black to black, and
green or bare wire to green.  

13.  Replace wiring box cover and screws.  Do not

pinch wiring under cover.

14.  Check for free movement of the damper before

installing housing cover and screws.

15.  Turn on power and check operation of the blower.
16.  Top and side flanges of the back plate may be

covered with trim strips.  Do not block grill opening at
bottom with trim.  It will adversely affect performance
of the blower. 

Black
to
Black

120 VAC
Line In

White
to
White

Green to
Green

11” (27.9 cm)
dia. hole

Guide
Hole

91

/

8”

(23.2 cm)

71

/

4” (18.4 cm)

11

/

4” (3.2 cm)

Dia. Hole

12 7/8”

(32.7 cm)

28 1/4”
(71.8 cm)

25” (63.5 cm)

10

3

/

4”

(27.3 cm)

WALL CUTOUT

Summary of Contents for VBCV3638

Page 1: ...Viking Installation Guide Designer Series Built In Custom Ventilator System...

Page 2: ...he National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities 3 When cutting or drilling into wal...

Page 3: ...stated 2 Duct run length is for general reference only for longer duct runs increase duct size and contact a qualified and trained installer Straight runs and gradual turns are best for example each 9...

Page 4: ...OOD INSTALLATION Plan where the ductwork will be located See pages 12 13 for rough in dimensions Install proper sized duct work and roof or wall cap for the type of blower you are using Adjust your me...

Page 5: ...s Make sure the back wall of the custom hood canopy is flush with the cutout so the ventilator system may be mounted as shown below Custom Hood Canopy 1 Position ventilator system inside of the custom...

Page 6: ...red by screw heads 2 Lift ventilator into position inside the hood 3 Fasten ventilator to four 4 THREADED STUDS using four 4 HEX NUTS provided 4 Plug ventilator s POWER CORD into RECEPTACLE inside the...

Page 7: ...n inside the hood 3 Engage 2 tabs on ventilator into 2 slots in top of hood 4 Fasten ventilator to two 2 THREADED STUDS using two 2 HEX NUTS provided 5 Plug ventilator s power cord into receptacle ins...

Page 8: ...tion below 4 Wire black to black white to white and green or bare ground to green ground screw provided Replace wiring box cover Make sure to connect remote wires to 2 prong male cord and service to 3...

Page 9: ...upper two thirds of the shingles around the cutout area Carefully lift the shingles to allow the back flashing sheet on the blower housing to fit under them 9 Center the blower ring in the 11 27 9 cm...

Page 10: ...cm diameter hole making sure that the 11 4 3 2 cm diameter electrical wiring hole aligns with the hole in the wiring box 9 Attach blower to the wall with the six screws provided It is recommended tha...

Page 11: ...the top and sides of the cutout area only Carefully lift the shingles to allow the back flashing sheet on the blower housing to fit under them 9 Center the blower ring in the 11 27 9 cm diameter hole...

Page 12: ...3 2 cm diameter electrical wiring hole aligns with the hole in the wiring box 9 Attach blower to the wall with the six screws provided All six holes in the back panel must be filled or any moisture th...

Page 13: ...243 4 62 9 cm 151 2 39 4 cm 281 4 71 8 cm DEV900 DEV1200 DEV1500 22 1 8 56 2 cm B 10 1 8 25 7 cm A 29 1 2 74 9 cm 10 25 4 cm Dia Opening for wiring Flashing Flashing Opening for wiring 3 1 2 8 9 cm 6...

Page 14: ...duct required 7 Round for External Ventilation Duct 16 40 6 cm 6 15 2 cm 6 1 8 15 6 cm A B C 120V 2 5 1 cm 3 4 1 9 cm 8 20 3 cm 5 12 7 cm 16 40 6 cm 6 15 2 cm 1 2 5 cm 11 3 4 29 8 cm For 900 or 1200...

Page 15: ...cm 11 3 4 29 8 cm For 880 CFM Internal and 1200 or 1500 CFM External Ventilation Installation For 880 CFM Internal and 1200 or 1500 CFM External Ventilation Installation 10 dia duct required 47 5 8 1...

Page 16: ...10 dia duct required Dim 36 W 42 W A 35 5 8 41 5 8 90 5 cm 105 7 cm B 34 5 8 40 5 8 87 9 cm 103 2 cm C 17 13 16 20 13 16 45 2 cm 52 9 cm 16 40 6 cm 6 15 2 cm A B C 2 5 1 cm 16 40 6 cm 6 15 2 cm A B C...

Page 17: ...M Internal and 1200 or 1500 External Ventilation Installation For 880 CFM Internal and 1200 or 1500 CFM External Ventilation Installation 10 dia duct required 24 61 0 cm 10 25 4 cm 53 5 8 136 2 cm 52...

Page 18: ...WIRING DIAGRAM BUILT IN DESIGNER HOODS REFER ONLY TO FEATURES EQUIPPED WITH THIS UNIT 18...

Page 19: ...8I PS042707J Viking Range Corporation 111 Front Street Greenwood Mississippi 38930 USA 662 455 1200 For more product information call 1 888 VIKING1 845 4641 or visit the Viking Web site at vikingrange...

Reviews: